010-619-J0 Rev B
Page 9
•
For voltages above 277Vac, power factor and total harmonic distortion may be derated. Up to
320Vac, the rectifier may not be operational but shall not suffer any damage.
3.1.8
AC Inrush/Transient Suppression
An external surge suppressor is not required at the AC input, modules are protected from input lightning
and transient surges in accordance with IEEE/ANSI C62.41 Category B3.
3.1.9
Soft Start
To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start,
sometimes referred to as “current walk-in”, works by gradually (up to five seconds) ramping the current
limit up from zero to the actual or defined customer setting. The rectifier output voltage is ramped up
from the minimum voltage to the float voltage.
3.1.10
Start Delay
The rectifier modules are equipped with a delay timer in order to stagger start a series of modules to
prevent excessive loading of generators upon start up. The built-in timer delays the turn on of the
module depending on the value selected (up to 120 seconds) via the controller. A minimum one-second
delay is preset to allow charging of the input capacitors.
3.1.11
Current Limit/Short Circuit Protection
The current limit function determines the maximum output current limit of the rectifier module, regard-
less of output voltage or power. Maximum output current is limited to a constant value down to short
circuit condition. Current limiting can be used to mate the rectifier output current ampacity to the needs
of the load and parallel battery to minimize excessive battery recharge current.
The rectifier will sustain a short circuit at the output terminals indefinitely. The maximum short circuit
current cannot exceed 105% of the rated full load current.
3.1.12
Power Limiting
Each rectifier module is designed to limit power output to the module specification. This enables more
current to be supplied at lower output voltages, and allows matching of output to the demand of constant
power loads, normally seen with telecom equipment.
This feature may also be used for a faster recharge of flooded batteries paralleled with the load.
NOTE
:
Current limiting overrides the power-limiting feature.
3.1.13
High Voltage Shutdown (HVSD)
This feature provides protection to the load from over voltage conditions originating from the rectifiers.
It operates by shutting down the offending rectifier module when a high output voltage condition occurs.
Indication is through the red Alarm (Module Fail) LED. Modules will restart automatically; however, if
more than three over voltage conditions occur in one minute, the module will latch off and remain shut
down until it is reset.
3.1.14
Battery Eliminator Operation
Rectifier modules maintain all specifications (except where indicated) with or without a battery attached
in parallel to the output; however, if a battery or another module supplying DC voltage in parallel is not
present, there will be no monitoring or control activity if there is an AC power failure or input fuse failure.
Summary of Contents for Cordex HP 48 1.2kW
Page 2: ......
Page 4: ......
Page 10: ...vi...
Page 14: ...010 619 J0 Rev B Page 4...
Page 16: ...010 619 J0 Rev B Page 6 Figure 1 Single Shelf Figure 2 Dual Shelf Figure 3 2RU Shelf...
Page 28: ...010 619 J0 Rev B Page 18...
Page 30: ...010 619 J0 Rev B Page 20...
Page 46: ...010 619 J0 Rev B Page 36...
Page 56: ...010 619 J0 Rev B Page 46...
Page 58: ...010 619 J0 Rev B Page 48...