4. Insert fuses into the slots.
The maximum allowable output current of the GMT block is 40A distributed over up to eight poles.
The bigger left pole can accommodate a current of up to 10A with a fuse of up to 15A. The smaller
poles can each accommodate a current of up to 8A with a fuse of up to 10A.
NOTE
:
When using the bigger left pole with a 15A fuse, always leave the adjacent position empty.
DC Output to Batteries
The wires must be UL approved XHHW or RHH/RHW (for Canadian users, RW90 Type). Double check
the battery polarity and then connect the positive cable to the top side of the output bar and negative
cable to bottom side.
Figure 20:
DC Output to Batteries
6.6.2
DC Output for Model 0300165 (maximum 4800W)
The DC cable connections to the system are made within, or just outside, the integrated distribution
module located on the right side of the shelf. To ensure proper access to connections, install DC cables
in the sequence described in this section.
WARNING
:
Leave cables disconnected at battery and verify output polarity using a voltmeter. Make
battery connections only after all other wiring is completed.
DC output wire shall be UL approved XHHW or RHH/RHW (Type RW90 for Canada)