010-619-J0 Rev B
Page 58
Mounting:
Modular on Cordex CXRF 48-1.2kW series shelves (options for 1RU horizontal
or 2RU vertical orientation depending on shelf)
Relay Outputs:
Seven (7) Form C, 60Vdc 1A maximum
Digital Inputs:
Two (2), 0 to 60Vdc
Analog Inputs:
One (1) DC voltage, 0 to 60Vdc One (1) DC current, ±50mV Two (2)
temperature, 0 to 20Vdc with power source
Communication
Ports:
Ethernet RJ-45, CAN (see shelf specifications)
Recommended Signal Wire Sizes
Wire Size Range:
#16 to #26 AWG (1.5 to 0.14mm2)
Temperature
Rating:
90°C (194°F)
CAUTION
:
TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm2) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering
information.Specifications are subject to change without notice.
Table 10:
Specifications: CXCM1+ Controller (Continued) (Sheet 3 of 3)