13
0913000-J0 Rev D
4.2 Distribution Section
The power systems are designed for high capacity distribution applications. Each distribution section can be
equipped with a variety of different fuse/CB panel combinations as shown in Table D and Figure 4.
Table D — Distribution Options per Section
Panel Type
Number of Positions per Section
TPL Fuses:
4 fuse positions per panel
Up to a maximum of 3* fuse panels per bay
Plug-in TLS/TPS fuses:
18 fuse positions per panel
Up to a maximum of 6** fuse panels per bay
Bolt-in high capacity breakers
12 breaker poles per panel
Up to a maximum of 3* fuse panels per bay
Plug-in bullet breakers
18 breaker poles per panel
Up to a maximum of 6** fuse panels per bay
*Up to a maximum of 2 panels per bay with the AC distribution option.
**Up to a maximum of 4 panels per bay with the AC distribution option.
Figure 4 — Example of distribution panels
TPL fuse panel
Shunt Multiplexer
Distribution panel
alarm indicators
Bolt-in breaker panel
4.2.1 Rectifier Alarms and LEDs
Rectifier status, such as Mains OK, Minor and Major alarms, display on the rectifier front panel. See the Cordex rec-
tifier shelf manual included with the system documentation package for detailed information.
x
A rectifier Major alarm indicates the module has shut down due to a critical fault.
x
A rectifier Minor alarm indicates the module has a noncritical alarm, but it has not shut down.