2. INSTALLATION
17
2.2
Tower Configuration Installation (Continued)
4. COMMUNICATION
44
The following are messages and descriptions for each group.
Line Status:
Normal: AC line is normal
Boost: AC line is out of tolerance, Boost mode in operation
Blackout: AC line non-exist
Low: AC voltage low
High: AC voltage high
Freq low: Line frequency too low
Freq high: Line frequency too high
Output Status:
Line mode
Inverter mode
Inverter mode, low batt. warning
Inverter mode (testing battery)
Boost mode
Hot swap mode
Shutdown due to fault
Shutdown due to low battery
Shutdown due to user request
Shutdown due to no line
Faults:
Vout_Abs: Output voltage absent/Output short circuit
Vout_Hi: Output voltage high
Vbat_Hi: Battery voltage high
Vbat_Lo: Battery voltage low
Temp_Hi: Ambient temperature high
Iout_Hi: Output current high
EEPROM_Flt: Error reading EEPROM
Wout_Hi: Output power high (overload)
Alarms:
Vout_Lo: Output voltage low
Iout_Hi: Output current high
Overload: Output overloaded
Temp_Hi: Ambient temperature high
Temp_Lo: Ambient temperature low
Pll: PLL can not lock
Line_Freq: Line freq high or low
Bat_Test: Failed battery test
4.2
RS-232 Communication (Continued)
7. Install two other braces to the outside of the UPS and EBP rear panels using
the screws shipped with the EBP.
Braces
EBP
Connector
Cable
Figure 2.5
Rear Installation
EBP
UPS