Introduction
Alpha Technologies
1.3
The Novus 1800TP UPS Front Panel (Continued)
Figure 1.3.4
RS–232 Connector
1.3.3: RS–232 Communications
8
Serial Interface
This DB–9 female connector is used to connect the unit to a host computer for remote
control, monitoring and calibration via RS–232 commands. Its layout and operation is
shown in Figure 1.3.5. A serial cable to connect it to a computer is available from Alpha.
More information on its connection and use is given in Section 4, “Communication.”
The interface is opto–isolated and shares a common ground with the
Status/Self Test Terminal Block.
8
Isolated
Ground
1
6
2
3
4
5
7
8
9
Relays Close On Alarm
Microprocessor
Low Battery
Alarm
Service
Alarm
Gnd
Rx
Tx
Isolated
RS-232
Isolated
+5 Vdc
Opto-
Isolator
Remote Inverter Off or Reset of Novus 1800TP
[Activated by +5 V applied for at least 0.3 sec]
Figure 1.3.5
Serial Interface Operation and Layout
NOTE:
100 mA (Max)
TIPS:
1)
The relays maximum
rating are 0.5 Amps at
125 VAC or 110 VDC.
2)
For the computer port
pin diagram, see Section
4.1, “Wiring the RS–232
Port,” Figure 4.1.1.