29
0170000-J0 Rev B
Table H — Specifications for 230 V models
Model number
AILI 750 VA
AILI 1000 VA
AILI 1500 VA
AILI 2200 VA*
AILI 3000 VA
Power rating, VA/W
750 VA
675 W
1000 VA
900 W
1500 VA
1350 W
2200 VA
1980 W
3000 VA
2700 W
Dimensions, W x D x H (mm)
Unit
440 x 405 x 88
440 x 405 x 88
440 x 650 x 88
440 x 650 x 88
Shipping
560 x 526 x 228
560 x 526 x 228
560 x 770 x 228 560 x 770 x 228
Weight (kg)
Unit
27
29
29
45
48
Shipping
29
31
31
47
50
Input AC Parameters
Surge protection
220 J
Voltage range without
battery operation
165 to 300, configurable
Frequency range
45 to 65 Hz, (±0.5Hz)
Input power cord
IEC-320-C14
IEC-320-C14
IEC-320-C20
IEC-320-C20
Output receptacles
(8) IEC-320-C13
(8) IEC-320-C13 (8) IEC-320-C13
(1) IEC-320-C19
(8) IEC-320-C13
(1) IEC-320-C19
Voltage (normal mode)
220 / 230 / 240 VAC (configurable) ±10%
Voltage (battery mode)
220 / 230 / 240 VAC (configurable);
±5% before low battery warning
Transfer time
4-6 ms typical
Waveform
Sine wave
Frequency (normal mode)
45 to 65 Hz, (±0.5 Hz)
Frequency (battery mode)
50 / 60 Hz, (±0.5 Hz), auto sensing
Overload Warning
Normal mode
> 100% to 109%
Continuous overload alarm and power to the load
> 110% to 120%
Shutdown after 10 minutes
> 120%
Shutdown UPS immediately
Battery mode
> 100% to 119%
Continuous overload alarm until end of battery
discharge
> 120% to 130%
Shutdown after 10 seconds
> 130%
Shutdown UPS immediately
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity x voltage x rating
2 x 24 x 7
3 x 36 x 7
3 x 36 x 9
6 x 72 x 7
6 x 72 x 9
Summary of Contents for Sentra 1000
Page 2: ......
Page 12: ...0170000 J0 Rev B 10 Step 3 Step 4 Step 5 ...
Page 26: ...0170000 J0 Rev B 24 5 3 Replacing Batteries STEP 1 STEP 2 STEP 3 750 1000 1500 VA ...
Page 35: ......