Tri Power X33 Mod HP Manual | Rev 1.20 | © Alpha Technologies GmbH 2013
Operating
a
nd Main
tena
nce
Manua
l
Tri Power X33 Mod HP
59
Bypass
Bypass
Enabling
If enabled, the UPS controls triggering of the bypass automatically. If disabled,
the UPS will never switch over to bypass and, therefore, in the case of a pro-
longed overload (see ‘Overloaded permitted’ in Chap. 10), or in the case of a
failure and redundancy absence, the UPS switches off.
Forced Mode If enabled, the UPS activates the bypass permanently
DIP Speed
It allows variation of the automatic bypass activation sensitivity (forced mode
disabled)
• SLOW: loads that are not sensitive to drops in voltage or
microinterruptions but which provoke frequent current peaks.
• STANDARD: normal uses.
• FAST: loads sensitive to the microinterruptions
Bypass Start
Mode
It can be enabled or disabled. Enabled the load will be supplied through bypass
before inverter starts.
ATTENTION
If the PLL function is disabled the automatic bypass function is disabled automatically as well. If the
overload is prolonged the UPS switches off (see ‘Overload permitted’ in the Technological Description
chapter).
Batteries
Threshold
Values
Autonomy end
warning
Setting the start time of the end of battery autonomy
warning [min.]
maximum battery
time
Maximum time te UPS run on battery [Sec]. After the
presetted time the UPS will switch off indepenently of
the battery capacity. In OFF position the function is di-
sabled.
Battery char-
ger
Charge in Standby
If enabled, it enables battery charging with the UPS off
Restart
Restart Enabling
Enables or disables restarting of the unit when mains
power returns after the batteries have run down
completely
Minimum autonomy Minimum percentage of autonomy to preserve
Total KB
Sets the total number of KBs installed (1 KB = 4 battery boxes) Necessary for the
UPS to supply correct autonomy values on the basis of the load applied
Capacity (*)
Sets the capacity value of the batteries in the UPS [Ah]
Load from archiv
Load discharge curve from archive
Discharge
curve
View from archive
View discharge curve from archive or in use
Custom
Power: capacity (Ah)
Data: 3 - maximal 20 data pairs (voltage/time)
1. pair (starting), last pair (end of discharge)
(*) Only available in „SERVICE-MODE"
ATTENTION
The correct numbers of strings and the correct battery capacity each string has to be given. A non correct infor-
mation can damage the battery system and/or the battery charging can be incorrect.