8. Diagnostics
Status
Indicator
Power Module-
LED(s)
Acoustic
Signal
Message on Display
Description and
operation advices
VIOLETT
intermittent
GREEN
fixed
-
BATTERY FAULT
The battery system has to be
checked
VIOLETT
intermittent
ORANGE
fast intermittent
-
USV ON BYPASS
The load is supplied through
bypass
VIOLETT
intermittent
ORANGE
fast intermittent
-
MANUELL BYPASS
The load is supplied through
manuel bypass
VIOLETT
short intermittent
-break
ORANGE
fixed
double intermit-
tent- break
AUTONOMY-RESERVE
Autonomy reserve. When
running on battery wrong
connection to the battery
RED
fixed
RED
fixed on one
Module
fast intermittent
CHARGER BROKEN
The charger secton on mini-
mum 1 module is broken
RED
fixed
ROT
fixed on one
Module
fast intermittent
MODULE FAULT
Minimum one module is fail.
Possible defects:
Inverter, Booster/PFC,
Communication between CM
and PM, Battery connection,
Mains connection, HVBus.
RED
fast intermittent
-
fast intermittent
BATTERIE KO
The battery system is broken
or not connected
RED
fast intermittent
RED
double intermit-
tent - break
fast intermittent
BATTERY VOLTAGE
HIGH
Battery voltage out of limits
(too high) - check
RED
fast intermittent
RED
double intermit-
tent - break
fast intermittent
HVBUS RUNAWAY
The voltage of HVBus is to
high - check
RED
fast intermittent
RED
double intermit-
tent - break with
Power module
in alarm
fast intermittent
OVERTEMPERATUR
The internal temperature is
to high - check enviroment
temperature or fans
RED
fast intermittent
RED
double intermit-
tent - break with
Power module
overload
fast intermittent
OVERLOAD
Load on minimum one Power
module to high
RED
fast intermittent
-
fast intermittent
FUNCTION CM KO
Communication failure bet-
ween PM and CM
RED
fast intermittent
-
fast intermittent
BACKFEED
Problem on BACKFEED PRO-
TECTION detected