8. Diagnostics
Message
Meaning
NO MAINS! START-UP NOT
ALLOWED
No mains supply. Start-up not allowed. To start the UPS on battery, select this
confi guration via the display.
EMERGENCY POWER OFF!
The Emergency Power Off (EPO) is working, the EPO command has been
given by a push button or a disconnecting switch on the input line was opened
while the UPS was working
CONFIG. INCOMPLETE FOR
START-UP!
The UPS requires a complete start-up confi guration.
THREE-PHASE CIRCUIT
SEQUENCE INCORRECT!
Invalid three-phase input sequence. It needs to be checked.
THE PMs´ SW VERSIONS ARE
INCORRECT: UPDATE THEM!
One or more Power Modules are programmed with an invalid SW version. An
update is necessary.
Start the UPS in the Service Mode and update the Power Modules.
START-UP ERROR!
An error occurred during start-up of the UPS.
UPS SHUT DOWN BY PROGRAM-
MING!
UPS shut down by programming.
SHUTTING DOWN DUE TO AN
INCORRECT CONFIGURATION
An error occurred in confi guration. UPS in shutting down.
SHUTTING DOWN DUE TO END
OF AUTONOMY
Battery charge level is too low, UPS in shutting down.
START-UP WITH BATTERY
FAILED
Start-up with battery failed.
MAXIMUM TIME ON BATTERY
Battery autonomy finished. The batteries must be changed.
MAXIMUM TIME ON RESERVE
Reserve autonomy time fi nished. The UPS is shutting down.
LOAD NOT FED
Load feeding interrupted.