40
Alpha 240XP and 240XE - Fault Finding
10.4 CENTRAL HEATING - Follow operational sequence
YES
YES
Turn thermostat to max.
External controls
calling for heat
If fitted, internal
clock calling for heat
240 V across main
terminal block,
terminals 1 and N
YES
Replace relay PCB
Relay energised
and contacts closed
i.e. continuity between
terminals 31, 32 on
PCB
NO
YES
Turn selector to and
go to section ' ', page 41
A
YES
Pump runs
NO
Go to section ' ', page 41
B
Primary flow switch operated
NO
YES
Go to section ' ', page 41
C
Fan runs at max. speed
NO
YES
Go to section ' ', page 41
D
Go to section ' ', page 42
J
Air pressure switch proved
Spark at ignition electrodes
for upto 10 seconds
Go to section ' ', page 42
L
YES
NO
NO
YES (240XE)
YES (240XP)
YES
Go to section ' ', page 41
E
Press red button to reset
NO
YES
(240XE only)
Burner lights
YES
Go to section ' ', page 41
F
Go to section ' ', page 42
I
Burner output modulates until
set temperature is reached
Burner goes out
NO
YES
Operation sequence successful
Pump continues to run for
5 minutes
YES
Go to section ' ', page 42
G
Go to section ' ', page 42
H
Red reset button
illuminated
But, burner does not stay
alight after 10 seconds
If still illuminated,
Go to section ' ', page 42
K
(240XE only)
YES (240XE only)
YES (240XP only)
Fan stops
Fan reduces to slow speed
YES
Summary of Contents for Alpha 240XE
Page 35: ...35 Alpha 240XP and 240XE Wiring Diagrams 9 2 ILLUSTRATED WIRING DIAGRAM Alpha 240XE ...
Page 36: ...36 Alpha 240XP and 240XE Wiring Diagrams 9 3 FUNCTIONAL FLOW WIRING DIAGRAM Alpha 240XP ...
Page 37: ...37 Alpha 240XP and 240XE Wiring Diagrams 9 4 FUNCTIONAL FLOW WIRING DIAGRAM Alpha 240XE ...