15
Technical features and dimensions
2.4.1 TECHNICAL DATA ACCORDING TO THE ERP DIRECTIVE
ARES TEC
150
230
300
348
400
500
600
Element
Symbol
Unit
Useful heat output
Nominal
output
kW
146
195
244
294
342
442
540
Room central heating seasonal energy
efficien
cy ηs
%
93
92
94
93
94
94
92
Central heating seasonal e
ffi
ciency class
A
A
A
A
A
*
*
For boilers for central heating and combination
boilers: useful heat output
Useful heat output in high temperature mode (Tr
60 °C / Tm 80 °C)
P
4
kW
136,3
209,3
274,5
341,4
373,0
441,9
540,3
Efficien
cy at nominal heat output in high temperature
mode (Tr 60 °C / Tm 80 °C)
η
4
%
87,8
88,1
88,3
88,4
88,4
88,5
88,5
Useful heat output at 30% nominal heat output in
low temperature mode (Tr 30 °C)
P
1
kW
45,2
68,8
91,5
113,2
124,0
147,1
175,7
Efficiency at 30% nominal heat output in low
temperature mode (Tr 30 °C)
η
1
%
97,0
96,6
98,1
97,7
98,0
98,2
96,0
Boiler with power range adjustment: YES / NO
NO
NO
NO
NO
NO
NO
NO
Auxiliary electricity consumption
At full load
elmax
kW
0,190
0,195
0,210
0,270
0,425
0,555
0,590
At partial load
elmin
kW
0,042
0,040
0,032
0,036
0,051
0,053
0,088
In standby mode
P
SB
kW
0,005
0,005
0,005
0,005
0,005
0,004
0,007
Other items
Heat loss in standby
P
stb
kW
0,32
0,39
0,34
0,95
0,95
0,95
1,34
Emissions of nitrogen oxides ref. PCI (PCS)
NOx
Mg/kWh
53
51
53
49
50
48
50
Annual electrical consumption
Q
HE
GJ
424
653
844
1054
1148
1358
1694
For mixed central heating appliances
Stated load pro
fi
le
-
-
-
-
-
-
-
Water central heating energ
y efficien
cy
η
wh
%
-
-
-
-
-
-
-
Daily electrical power consumption
Qelec
kWh
-
-
-
-
-
-
-
Daily fuel consumption
Qfuel
kWh
-
-
-
-
-
-
-
Sound power level indoors
Lwa
dB (A)
-
-
-
-
-
-
-
Annual electrical consumption
AEC
kWh
-
-
-
-
-
-
-
Annual fuel consumption
AFC
GJ
-
-
-
-
-
-
-
DHW seasonal e
ffi
ciency class
-
-
-
-
-
-
-
* (Devices not covered by directive 2009/125/EC)
Summary of Contents for ARES Pro 150
Page 2: ......