Chapter 2 Installation and Wiring
18
power supply of driver and the wiring method is shown in Figure 2-13.
5V
+24V
24V
DO
COM
Relay
R
Fig. 2-13 On-off output connection mode 1 of multi-function output terminals
2) Multi-function output terminals DO as discrete output can also use the external,
9~30V, power supply and the wiring method is shown in Figure 2-14
COM
DO
24V
+24V
5V
Relay
DC 9
~
30V
+ -
R
Fig. 2-14 On-off output connection mode 2 of multi-function output terminals
●
Wiring of Relay Output Terminals TA, TB, TC
To drive inductive loads (e.g. electromagnetic relays, contactors), it is suggested to
add surge voltage absorption circuit, such as the RC absorption circuit, piezoresistor
or flywheel diode (pay attention to the diode polarity when used for DC
electromagnetic circuit), etc. Components of absorption circuit should be installed
close to both ends of coil of relay or contactor.
Tips
1. Don’t short circuit terminals 24V and COM, otherwise the control board may be
damaged.
2. Please use multi-core shielded cable or multi-stranded cable (above 1 mm) to
connect the control terminals.
3. When using a shielded cable, the shielded lay’s end that is nearer to the driver
should be connected to PE.
4. The control cables should be as far away (at least 30 cm) from the main circuit and
high-voltage cables as possible (including power supply cables, motor cables, relay
cables and cables of contactor). The cables should be vertical to each other to
reduce the disturbance to minimum.
2.6 Wiring of Driver for Basic Operation