Chapter 4 Parameter Index
28
Function
code
Parameter
Setting range
Factory
setting
Modify
flag
Modbus
address
P0.09 Basic
frequency 0.10~400.0Hz 50.00Hz
×
0109
P0.10
Maximum output
frequency
MAX [50.00Hz, upper limit
frequency, digital setting
frequency, Multi-step
frequency, jump frequency] ~
400.0Hz
50.00Hz
× 010A
P0.11 Motor
type
0: General Motors
1: A motor
2: B motor
0 ×
010B
P0.12~
P0.13
Reserve -
- -
P0.14
Rated voltage of
motor
60~480V
Rated
voltage
× 010E
P0.15 Reserve
-
-
-
P0.16
Maximum output
voltage
60~480V
Rated
voltage
× 0110
P0.17
Keypad knob
adjusting rate
0: Keypad knob integral
regulation;
(1~250) * (0.01Hz | 1rpm)
0 ×
0111
P0.18
Acceleration time
1
0.1~3600s
6.0s
○
0112
P0.19
Deceleration time
1
0.1~3600s
6.0s
○
0113
P1: Start-stop control
Function
code
Parameter
Setting range
Factory
setting
Modify
flag
Modbus
address
P1.00 Start
mode
0: Start from the start-up
frequency
1: First brake (excitation), and
then start at the start-up
frequency
1
○
0200
P1.01~
P1.03
Reserve -
- -
P1.04
Start-up DC
braking hold time
0.0~30.0s 0.3s
○
0204
P1.05~
P1.06
Reserve -
- -
P1.07
Acceleration and
deceleration
mode
0: Linear 1: S curve
0
○
0207
Summary of Contents for AS600M Series