Chapter 5 Detailed Function Introduction
49
Chapter 5 Detailed Function Introductions
5.1 Basic Function
P0.00 Menu display mode
Setting range: 0~1 [0]
0: Standard menu
1: Check mode menu
Notes:
When P0.00 is set to 1, the display enters the check menu mode. In this mode, you
can view and modify each modified function code by the knob adjustment. The
remaining unmodified function codes will not be displayed unless you change the
setting to 0 again.
P0.01 Control mode
Setting range: 0~3 [2]
0: V/F control
1: vector control
2: Reserve
3: V/F separation control
Notes:
V / F Control:
VVVF ordinary open-loop control
Closed-loop Vector Control: Speed sensor vector control mode is for high
perfomance occasion.
V/F Separation Control: This control mode can be used in some places where the
frequency and the voltage are required to control independently.
P0.02 Frequency digital setting
Setting range: 0.00Hz ~Maximum frequency
[0.00Hz]
Notes:
When P0.03 = 1, the keypad can be used to set frequency digital.
Tips:
The P0.02 ,which is changed by the digital knob on the keypad, can work immediately.
If "ENTER" is pressed , the value will be stored into the inverter’s internal EEPROM
and will not be lost even power outage.
P0.03 Frequency setting source 1 Setting range: 0~5 [1]
0: NULL
1: Frequency digital setting, digital knob
adjustment
2: Unipolar analog
(
AI1
)
3: Bipolar analog
(
AI2
)
4: Pulse input
5: Communication setting