Appendix 2 Use of MODBUS Communication
90
List of Data:
Command Data (writable)
MODBUS
Address
Name
bit
Content
0000H
(
Reserved)
0001H
Operation
Signal
0
Operation Command
1: Operation
0: Stop
1
Reverse Command
1: Reverse
0: Forward
2
External Fault
1: External Fault (EFO)
3
Fault Resetting
1: Fault Resetting Command
4
Multi-functional Input Command 1
(P3.01 X1Terminal Function)
5
Multi-functional Input Command 2
(P3.02 X2Terminal Function)
6
Multi-functional Input Command 3
(P3.03 X3Terminal Function)
7
Multi-functional Input Command 4
(P3.04 X4Terminal Function)
8
Multi-functional Input Command 5
(P3.05 X5Terminal Function)
9
Multi-functional Input Command 6
(P3.05 X5Terminal Function)
A
Multi-functional Input Command 7
(P3.05 X5Terminal Function)
B~
F
Reserved (See below Note 1)
0002H Speed
Command
0003~001FH Reserved
Note 1: write “0” in the reserved BIT.
Note 2: when the communication frequency command is > the maximum frequency,
the abnormality code 21H “Beyond the Upper & Lower Limit” will be reported and the
operation frequency will be reserved unchanged.
Note 3: addresses of 000DH~0011H and 0013H~001FH are reserved in the general
driver.
Note 4: when the above reserved register addresses are read, address error will be fed
back.