Appendix 2 Use of MODBUS Communication
92
MODBUS
Address
Name
bit
Content
0021H
Fault
Content
8 Hardware Abnormality (CCF3~CCF6)
9 Motor Overload (OL1)
A Input/ Output Phase Loss or Imbalance (SP1~SP2)
B Busbar Under-voltage (Uu1)
C Control Circuit Under-voltage (Uu2)
D Charging Circuit Under-voltage (Uu3)
E Grounding GF or Load Short Circuit (SC)
F (Reserved)
0022H
Alarm
Content
0 Busbar Under-voltage Alarm( Uu)
1 Driver Overload Pre-alarm (OLP2)
2 Analog Signal 1 Abnormality (AE1)
3 Reserved
4 Temperature too high (OH2)
5
The serial communication doesn’t receive the normal control
signal (CE)
6 The function code setting is inappropriate SF1
7 The operation mode is inconsistent with the terminal setting SF2
8
Output terminal setted up 26 can’t up to 4 sets of SF3 ,and it setted
up 27 can’t up to 3 sets of SF3.
9 Motor Parameters Tuning Abnormality
A Analog signal 3 Abnormality
B~F (Reserved)
0023H Before
the
frequency command compensation
0024H
After the frequency command compensation
0025H
AI1 Analog Input (V), 0~10.00V corresponding to 0~1000
0026H
AI2 Analog Input (V), 0~10.00V corresponding to 0~1000
0027H
Output Current (A)
0028H
Output Voltage (V)
0029H
Set Frequency Hz
002BH
Multi-functional Input
Term
inal
S
tat
e
0 Terminal X1
1: Close
0: Open
1 Terminal X2
1: Close
0: Open
2 Terminal X3
1: Close
0: Open
3 Terminal X4
1: Close
0: Open
4 Terminal X5
1: Close
0: Open
5 Terminal X6
1: Close
0: Open
6 Terminal X7
1: Close
0: Open
7~F (Reserved)
002CH
(Reserved)
Summary of Contents for AS600M Series