Appendix 2 Use of MODBUS Communication
93
MODBUS
Address
Name
bit
Content
002DH
Multi-functional Output
Term
inal
S
tat
e
0 DO
1: “ON”
0: “OFF”
1
BRA-BRB-BRC Relay ( Reserved only 3040GB and below
1:”ON” 0:”OFF”)
2 TA-TB-TC Relay
1: “ON”
0: “OFF”
3 Y1 Relay ( Reserved only 3040GB and below 1:”ON” 0:”OFF”)
4 Y2 Relay ( Reserved only 3040GB and below 1:”ON” 0:”OFF”)
5 Y3 Relay ( Reserved only 3040GB and below 1:”ON” 0:”OFF”)
6-F Reserved
002EH
AO1 Analog Output (V) 0~10.00V corresponding to 0~1000
0031H
DC Main Bus Voltage
0032H Output
Torque
0033H
Current Rotating Speed
0034H
Set Rotating Speed
0035H
Operating Linear Speed
0036H
Set Linear Speed
0037H Output
Power
003CH External
Count
Value
003D~
003FH
(Reserved)
0040~
004AH
Terminal State, 0040H~004AH corresponding to BIT0~BITA bit of 002BH in
order
004B~
00FEH
(Reserved)
List of Modbus Register Addresses:
Function Code Form Parameter
Code(DEC)
Modbus Register Address(HEX)
(Saving Confirmed)
(00FFH)
(Command Data)
(0001H~001FH)
(Monitoring Content)
(0020H~004FH)
P0.00
~
P0.19 0100H
~
0113H*
P1.00
~
P1.23 0200H
~
0217H
P2.00
~
P2.50 0300H
~
0332H
P3.00
~
P3.36 0400H
~
0424H
P4.00
~
P4.35 0500H
~
0523H
P5.00
~
P5.36 0600H
~
0624H
P6.00
~
P6.18 0700H
~
0712H
P7.00
~
P7.28 0800H
~
081CH
P8.00
~
P8.28 0900H
~
091CH
P9.00
~
P9.21 0A00H
~
0A15H
PA00
~
PA.30 0B00H
~
0B1EH