background image

17

C048-781-30 R01, Rev. B (01/2020)

5.4  

5.4  Bus Calibration

Bus Calibration

To access bus calibration settings from the home screen, 

press the Settings icon, then press Bus Calibration.

5.4.1 

5.4.1  Bus Load

Bus Load

Bus Load can be adjusted up to +/- 15 increments (+/- 15A). 

Voltage adjustment offset is shows on the right side of the 

display.

5.4.2 

5.4.2  Bus Voltage

Bus Voltage

Voltage can be adjusted up to +/- 30 increments (+/- 3.0V). 

Voltage adjustment offset is shown on the right side of the 

display. 

5.5  

5.5  System

System

To access system settings from the home screen, press the 

Settings icon, then press System. 

5.5.1 

5.5.1  Display

Display

5.5.1.1 

5.5.1.1  Brightness/Buzzer Volume

Brightness/Buzzer Volume

The display brightness and buzzer volume can be adjusted by 

moving the sliders. 

5.5.2 

5.5.2  Touch Calibration

Touch Calibration

This setting prompts user for permission to proceed with touch 

calibration. Follow instructions on screen to continue.

5.5.3 

5.5.3  Settings

Settings

5.5.3.1 

5.5.3.1  Input Feeder Size

Input Feeder Size

Press the SET button to adjust feeder fuse size for A1, A2, B2, 

and B1 busses.

1. 

Use keypad to enter a feeder fuse size between 100A and 

300A. 

2.  Press SAVE button to save feeder fuse size, or CANCEL 

to revert back to old feeder fuse size.

5.5.3.2 

5.5.3.2  Input Feeder Threshold

Input Feeder Threshold

Press the SET button to adjust feeder fuse threshold for A1, 

A2, B2, and B1 busses.

1. 

Use keypad to enter a feeder fuse threshold between 40% 

and 100%. 

2.  Press SAVE button to save feeder fuse threshold, or 

CANCEL to revert back to old feeder fuse threshold.

5.5.3.3 

5.5.3.3  Bus Redundancy

Bus Redundancy

Turn bus redundancy ON/OFF by pressing the check box next 

to Bus Redundancy. 

Figure 18.  Bus Load 

Calibration

Figure 19.  Bus 

Voltage Calibration

Figure 20.  Display

Figure 21.  Touch 

Calibration

Figure 22.  Settings

Figure 23.  Input 

Feeder Size

Figure 24.  Input 

Feeder Threshold

Summary of Contents for C016-2040-10

Page 1: ...v30 30 Distribution Panel For Telecom Broadband Technical Manual Effective January 2020...

Page 2: ...afety information to PREVENT INJURY OR DEATH to the technician or user WARNING FUMES HAZARD FIRE HAZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to the technician or...

Page 3: ...lease contact Alpha Technologies Services Inc or your nearest Alpha representative Alpha shall not be held liable for any damage or injury involving its enclosures power supplies generators batteries...

Page 4: ...ng the Network Cable 10 4 7 Output Connections 10 4 8 Circuit Breaker Installation 11 4 9 Polarity Check 11 4 10 Display Power 11 4 11 Installation Checklist 11 5 0 Operation 12 5 1 Overview 12 5 1 1...

Page 5: ...5 4 Information 18 5 6 Advanced 18 5 6 1 Raw Data 18 5 6 2 Configuration 18 5 6 3 Test Modes 18 5 6 4 Restore Defaults 18 5 7 Review System Status via the Embedded Web Server 19 5 7 1 Default Static...

Page 6: ...breaker position 4RU distribution panel with 40A connectorized outputs and an advanced touch screen display Breakers are available for this panel in ratings from 2A up to 30A 2 2 2 2 Features Feature...

Page 7: ...sembly the operating ambient temperature of the rack environment may be greater than room ambient Therefore take care to install the equipment in an environment compatible with the maximum ambient tem...

Page 8: ...into the mounting ears see Figure 3 4 3 4 3 Chassis Ground Chassis Ground DO NOT ENERGIZE THE PANEL BEFORE CHASSIS GROUND IS CONNECTED CAUTION The chassis ground is located in the side of the panel A...

Page 9: ...BLES HAVE HEAT SHRINK APPLIED PRIOR TO TERMINATION AND THAT NO OXIDE COMPOUND IS APPLIED TO ALL COPPER TO COPPER CONNECTIONS NOTICE Table 3 Input Termination Specifications TERMINATION TYPE HOLE STUD...

Page 10: ...f remote monitoring over the network is required complete the following steps to connect the Ethernet module with embedded web server NOTE For initial configuration it is recommended to use a crossove...

Page 11: ...then tighten the captive screws 4 9 4 9 Polarity Check Polarity Check The v30 30 includes a set of LED indicators inside of the panel to ensure correct polarity of the input terminations see Figure 11...

Page 12: ...LARMS Adjustable overload alarm threshold per bus 40 100 Bus overload Bus overload Warning 10 of alarm threshold Over voltage greater than 56 0 V Under voltage less than 47 0 V Bus redundancy Bus redu...

Page 13: ...and Warning Alarms In alarms list bus and module will be displayed for module in overload 5 1 2 5 1 2 Firmware Icons Firmware Icons 5 1 2 1 5 1 2 1 Alarm Icons Alarm Icons Alarm icons appear when at l...

Page 14: ...minor alarm bus overload warning Red Bus in major alarm bus overload and or high or low voltage 5 2 2 5 2 2 Display Per Breaker Status Display Per Breaker Status Asterisks indicate that each channel...

Page 15: ...jor alarm has been detected Orange White Gradient At least one minor alarm has been detected and no major alarm 5 3 5 3 Module Detail Module Detail To access this screen press any breaker status icon...

Page 16: ...back to old ampacity 5 3 2 2 5 3 2 2 Breaker Load Breaker Load Breaker load calibration can be adjusted by pressing the plus and minus buttons 5 3 2 3 5 3 2 3 Alarm Threshold Alarm Threshold Individua...

Page 17: ...user for permission to proceed with touch calibration Follow instructions on screen to continue 5 5 3 5 5 3 Settings Settings 5 5 3 1 5 5 3 1 Input Feeder Size Input Feeder Size Press the SET button t...

Page 18: ...m system monitoring Busses with at least 20V cannot be removed from configuration Modules and busses are automatically inventoried if data is being received by the controller 5 6 3 5 6 3 Test Modes Te...

Page 19: ...rimary DNS 192 168 123 1 y Secondary DNS 8 8 8 8 Once you establish a connection to the embedded Ethernet module use the following credentials to gain access to the protected data and administrative p...

Page 20: ...tination address y Configure email settings y Configure SMTP server y Enter user name email address and password y Enter email recipients y Send test email message Note SMTP server must be configured...

Page 21: ...Up to 60 30A 30B Input Current 300A max per input 600A max total load Load Per Circuit 35A max Maximum Input Interruption Device 375A MECHANICAL Dimensions L x H x D 19 x 7 x 13 2 18 w lacing bar Wei...

Page 22: ...ote Temperature Sensor Kit Includes 2 Probes 1 7ft Sensor to Sensor Cable 1 20ft Sensor to Sensor Cable C016 2032 10 Secondary Remote Temperature Sensor Kit Includes 2 Probes 1 7ft Sensor to Sensor Ca...

Page 23: ...Blue Black C745 424 10 Red Red Tracer C745 438 10 Blue Blue Tracer C745 434 10 12 7 Red Black C745 421 10 Blue Black C745 425 10 Red Red Tracer C745 298 10 Blue Blue Tracer C745 299 10 12 Red Black C...

Page 24: ...alarm monitoring 8p8c RJ 45 modular jacks 10 Circuit breaker positions A1 11 Circuit breaker positions A2 12 Circuit breaker positions B2 13 Circuit breaker positions B1 14 Output power B1 15 Output...

Page 25: ...25 C048 781 30 R01 Rev B 01 2020 Appendix B Appendix B One Line Diagram One Line Diagram...

Page 26: ...Technical Support 1 800 863 3364 For more information visit our website at www alpha com 2020 Alpha Technologies Services Inc All Rights Reserved Trademarks and logos are the property of Alpha Techno...

Reviews: