9400001-J1 Rev F
60
10.5 Shelf ID Connection
The shelf/bay ID module comes factory installed. If shelves are installed in more than one bay, then set the Bay ID
sequentially on each Shelf ID board.
Bay ID Display
Up Button
Reset Button
Down Button
Shelf ID board RJ12 connection
located on right side of rectifier shelf
(pre-installed from the factory)
IP
2 x 12kW
Rectifier
Slot IDs
2 x 12kW
Rectifier
Slot IDs
Bay ID 1
Shelf ID 1
Bay ID 1
Shelf ID 1
Bay ID 1
Shelf ID 2
Bay ID 1
Shelf ID 2
CAN driver
Cordex HP
J1
J12
J11
J10
J2 J3 J4 J5 J6 J7 J8 J9
CAN bus (transmits bay ID, shelf ID and rectifier slot IDs to CXC HP)
Rack-mounted Shelf ID
PCB
Bay ID 1
(manually set)
Figure 52 — Example of a Single Bay with Two Rectifier Shelves.