22
Alpha E-Tec 25R - Installation
PM length = C + (1 x 93° bend = 1.3 m) + (2 x 45° bends = 1.8 m)
C
Min.
400 mm
CD Easy-Flue
Flue sealing collar
Terminal end section
from CD Easy-Flue
PM length = C + (2 x 93° bend = 2.6 m) + (2 x 45° bends = 1.8 m)
C
Terminal end section
from CD Easy-Flue
PM length = C + (4 x 93° bend = 5.2 m)
C
Terminal end section
from CD Easy-Flue
Ensure there is a slope of approximately
3° back towards the Easy-Flue
Fig. 5.13
Note:
The equivalent horizontal flue assembly the equivalent plume management length (PM length) must not
exceed the maximum flue length stated for each boiler, i.e.
E-Tec boilers - the maximum equivalent flue length must not exceed 12 metres.
Note:
1. Ensure each joint is
secured with the screw
supplied.
2. Ensure there is always
a slight slope towards
the CD Easy-Flue so
that there is no part
of the pipework where
condensate will collect.