6.13 PROGRAMMING THE PCB
The boiler has the ability to programme several operational parameters. By modifying these parameters as
described below, the boiler can be adapted according to specific needs.
Parameter Setting
To activate the parameter menus the DHW control knob must be set to 6 o'clock and the CH control knob set to 9 o'clock
positions, then press button D (summer/winter) and button B (reset) simultaneously for 8 seconds. See Fig. 6.4. Now
activated, the screen will display the parameter group and parameter number followed by the parameter value.
There are three settable parameter groups 'SX', 'PX' and 'tX'. To scroll through the parameters press button D (summer/
winter) for 1 second. Once the parameter group is selected you can turn the CH control knob to select the parameter that
needs to be adjusted. To adjust the selected parameter turn the CH control knob until the required value is obtained, this will
be indicated by a fast flashing of the new value. To confirm the new value press the button B (reset) until '88' is shown on the
screen for 2 seconds followed by the parameter number and new setting flashing alternately on the screen. Once the new
parameter values have been entered press the button D (summer/winter) and button B (reset) simulataneously for 4 seconds
to exit the parameter menu.
Note:
When setting the parameters on a new PCB - set the values starting at the lowest parameter first.
Alpha E-Tec 25R - Commissioning
DHW control
knob
CH control
knob
RESET
INFO
RESET
BOOST
bar
°C
x100rpm
Button A
Button B
Button C
Button D
Fig. 6.4
ID
Parameter
Description
Range
0 - 60 (600s)
(10 sec steps)
0 - 84 (840s)
(10 sec steps)
0 - 60 (600s)
(10 sec steps)
0 - 2
0 - 1
The boiler has electronic timing, which prevents the burner from
cycling too often in central heating mode
In central heating mode the boiler performs a timed ramp up in
order to reach the maximum output set
The boiler is set to switch-on immediately after a request. For
zoned or complex systems with motorised and thermostatic
valves it may be necessary to delay ignition to prevent
overheating
Display lighting mode
0 Automatic
- The display lights up during use and dims after 15
secs of inactivity. In the event of an anomaly the display flashes.
1 Low
-
The display is always lit with low intensity
2 High
- The display is always lit with high intensity
LCD display setting
'Summer' mode
0
- The display is always off
1
- Displays the flow temperature during operation and off when
no request
'Winter' mode
0
- The display shows the set value of the CH selector
1
- The display shows the flow temperature during operation and
the set value with no request
CH ignition timer
CH ramp timer
CH ignition
delay from room
thermostat and
remote control
Display lighting
Display
t0
t1
t2
t3
t4
Default
18
(180s)
18
(180s)
0
0
1