Battery Installation / Replacement Procedure

1.  Connect the wire harness to the battery.

2.  Install the charged battery (a fully charged battery reads about 13Vdc) in the cradle as shown in Fig. 8. 

The locking tab secures it in place.

3.  Replace the battery compartment door. To replace the front cover, align the hinges with the hinge sockets 

and press them in with the door perpendicular with the main housing. Rotate the door closed until the 
closure door latches.

4.  Plug the FPR1207-F into AC Power. The Green LED should light.

5.  Verify the unit is functioning properly by unplugging the unit. The alarm should sound for one second and 

the Green LED should fl ash. The unit will be running on standby battery power.

6.  Re-plug the FPR1207-F into an AC power outlet. The unit is ready to be placed into service.

Fig. 6, 7.2Ah Battery

2

Fig. 2, FPR1207-F Dimensions (in/mm) 

(viewed from Back)

3

Risk of explosion if battery is replaced by an incorrect type. Recycle spent batteries in 
accordance with local regulations.

WARNING!

7.8"

198mm

3.0"

76mm

2.5"

63.5mm

2.4"

61mm

3.0"

76mm

1.3"

33mm

8.7"

221mm

1

1

2

2

Ø.380"

.200"

Ø.250"

Mounting holes for customer-supplied #12 hardware or equivalent

"Keyhole" slots for easy mounting

1

2

Fig. 3, RF cable connection

Fig. 5, AC Power Cord Connection

(viewed from Back)

Fig. 7, Battery Compartment, 

with wire harness

R

Remove cover to access 
silence alarm and battery 
emergency use buttons.

FPR1207-F Controls and Indicators

VISUAL STATUS INDICATORS

1

Green LED: 

AC mode

Green LED fl ashing: Battery mode
Red LED:

Failed self test

Red LED fl ashing:

Battery missing / Low battery

2

1

2

1

Fig. 8, Battery 

installed

010-344-B0-001 Rev. A 01/2011

010-344-B0-001 Rev. A 01/2011

Silence Alarm

Batter

y

Emergency

Use

Silence Alarm

Batter

y

Emergency

Use

Silence

Alarm

Batter

y

Emergency

Use

Fig. 4, Push Button Detail

2

Reviews: