11

010-353-B9-001 Rev. A1 (09/2015)

2.0 

Installation, continued

2.1  Installation and connection, 

continued

Pin 

Connection

Wire gauge

1

Positive (+)

16AWG

2

Negative (-)

16AWG

3

Signal Return

24AWG

4

AC FAILURE

24AWG

5

REPLACE BATTERY

24AWG

6

BATTERY MISSING

24AWG

7

BATTERY LOW

24AWG

7

6

5

4

3

2

1

1

8

7

6

D.  Determine the necessary cable length to provide appropriate service loops between the unit, 

the ONT, and the AC receptacle. Plug the line cord into the receptacle (1) in the unit. Secure 

line cord at one of the cable tie holes (2) with one included cable tie. 

DO NOT plug the unit 

into an AC receptacle until the last step of the installation procedure.

E.  Connect the output cable to the 12Vdc output connection (3) and to the coaxial connector (4). 

Secure in cable dressing holes (5) with the 

included cable ties.

1
2

4

3

3

4

2

Cable tie holes (2 plcs.)

Optional battery strap slot (1 of 2)

Mounting holes

Battery retaining clip

5

6

7

AC line cord connection 

Cable tie holes 

(on back of unit)

7-pin output cable connection

F-type coaxial connector

Fig. 2-2 FlexPoint connections and components 

5

8

F. 

Mount to the wall with customer-supplied #12 hardware or equivalent, using the keyholes (7) 

for easy mounting. For applications with higher seismic requirements, use the round hole in 

the back of the unit for direct fastening to a stud or other structural feature.

Fig. 2-3 12Vdc output connector pin numbers

Table 2-1 12Vdc output connector pin assignments

Summary of Contents for FP1208-F-5A

Page 1: ...FlexPoint TM Series UPS Technical Manual FlexPoint 1208 F 1232 D 1250 D Series Indoor UPS Effective September 2015...

Page 2: ...ZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to the technician or user WARNING FIRE HAZARD WARNING FIRE ELECTRICAL HAZARD ATTENTION The following sections contain i...

Page 3: ...Alpha Technologies or the nearest Alpha representative Alpha shall not be held liable for any damage or injury involving its enclosures power supplies generators batteries or other hardware if used or...

Page 4: ...ery options 8 Table 2 1 12Vdc output connector pin assignments 11 Table 3 1 Audible alarms and visual indicators 14 Table 3 2 FlexPoint battery options 14 Table of Contents FlexPoint safety and compli...

Page 5: ...signed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in...

Page 6: ...0Hz power receptacle provides primary power to the input of the unit The AC voltage is then converted to a usable 12Vdc output The power supply is to be installed within 8 2 4m of an AC receptacle Cur...

Page 7: ...either 32W or 50W respectively of 12Vdc primary and standby power for FTTx and RFoG activity The FP1208 F provides 8W of 12Vdc standby power for RFoG applications 5 1Ah 7 2Ah and 8 0Ah battery options...

Page 8: ...ceptacle Plug the line cord into the receptacle in the unit Secure line cord at one of the cable tie holes with one included cable tie Do not plug the unit into an AC receptacle until the last step of...

Page 9: ...2015 7 48 190 0 mm 3 19 81 0 mm 4 23 107 4 mm 6 57 166 9 mm 2 52 64 0 mm 2 83 71 8 mm 4 29 108 9 mm 3 23 82 0 mm Cover removed for clarity 1 0 Introduction continued 1 6 FlexPoint dimensions Fig 1 5...

Page 10: ...t the cord is easily accessible Always mount the unit in a vertical orientation with 6 15 2 cm of space above and below 2 4 5 10 cm in front and 2 5 cm of space on both sides to provide adequate therm...

Page 11: ...f the installation procedure E Connect the output cable to the 12Vdc output connection 3 and to the coaxial connector 4 Secure in cable dressing holes 5 with the included cable ties 1 2 4 3 3 4 2 Cabl...

Page 12: ...ry in place 3 Connect the battery wires to the battery terminals see Fig 2 5 To ensure correct wire connections verify the battery polarity clip is connected to the negative battery terminal 4 Install...

Page 13: ...tacle Within approximately 30 seconds the alarm should sound for 1 second it may take longer to trigger this alarm if the load is very light or not connected AC mode LED Green will display then turn o...

Page 14: ...er supply needs to be replaced REPLACE BATT LED Red steady ON 2 beeps every 15 minutes The unit automatically initiates a battery test every 180 days If the unit fails the test this alarm is triggered...

Page 15: ...e the test is postponed until those conditions are met If the AC input is lost or the unit is overloaded during the battery test it will be aborted and post poned until conditions are valid Once a bat...

Page 16: ...attery lb kg 1 2 0 54 5 1Ah Battery weight lb kg 3 9 1 8 7 2Ah Battery weight lb kg 5 7 2 6 8 0Ah Battery weight lb kg 5 73 2 76 Estimated Battery Runtimes 1 5W Load 4W Load 5 1Ah Battery Hrs 34 2 12...

Page 17: ...r 5 7 2 or 8Ah Battery L x W x D in mm 6 6 x 7 5 x 3 2 167 6 x 190 5 x 81 3 Unit Weight without Battery lb kg 1 3 0 59 5 1Ah Battery Weight lb kg 3 9 1 8 7 2Ah Battery Weight lb kg 5 7 2 6 8 0Ah Batte...

Page 18: ...7 2 or 8Ah Battery L x W x D in mm 6 6 x 7 5 x 3 2 167 6 x 190 5 x 81 3 Unit Weight without Battery lb kg 1 4 0 64 5 1Ah Battery Weight lb kg 3 9 1 8 7 2Ah Battery Weight lb kg 5 7 2 6 8 0Ah Battery...

Page 19: ......

Page 20: ...se Thorley Bishop s Stortford Hertfordshire CM22 7PA United Kingdom Tel 44 1279 501110 Fax 44 1279 659870 Alphatec Ltd 339 St Andrews St Suite 101 Andrea Chambers P O Box 56468 3307 Limassol Cyprus Te...

Reviews: