background image

15

010-353-B9-001 Rev. A1 (09/2015)

3.0 

Operation, continued

3.4  Operational modes

3.4.1   Normal mode 

This mode is defined as a state where the load is being supplied from AC input, and the battery is floating, 

charging or in the process of being tested.
When the unit is initially powered up, or whenever the input supply has been restored after an outage, the unit 

operates in charge mode. Once the battery voltage has reached the full charge voltage, the unit switches to 

float mode. If the input voltage is less than the minimum AC input, the system switches to operating in back-

up mode.
After approximately 180 days of operation, the battery is automatically tested to determine whether it has 

adequate capacity. It is tested when the following conditions are met: 

The battery is operating in float mode for 24 hours; and,
The battery is fully charged in the temperature between 5°C to 35°C / 40°F to 95°F for 24 hours

.

The Replace battery alarm is not active 

(triggered if the power module charger is in accept mode for 1 hour 

with the battery below 10.5V).

The Power module over voltage is not active 

(where the power module output is higher than the target by 

500mV for 75 seconds).

If the above conditions are not met when the test becomes due, the test is postponed until those conditions 

are met. If the AC input is lost, or the unit is overloaded during the battery test, it will be aborted and post-

poned until conditions are valid.
Once a battery test has been successfully executed, another test will be automatically scheduled to occur in 

180 days, without regard to the test results.

3.4.2   Back-Up mode

The load is being supplied from the battery while the battery voltage is greater than 10.5Vdc. When the bat-

tery falls below this value, it is disconnected.

3.4.3   Charging mode

This maintains the battery at 100% capacity. After an AC outage, when AC is present, the charger continues 

charging until one of the following occurs:

• 

Battery has reached 100% capacity.

•  Charging is reduced to float charge level. Normal BULK charge current is approximately 800mA. 
• 

When in ACCEPT MODE the current falls below 150mA, the mode changes to FLOAT. In the event 

the current does not reduce, the software triggers the mode change after 48 hours in ACCEPT

• 

Another power failure occurs requiring battery support.

No special action is required to restore normal operation once primary power is restored.

3.4.4   Mute mode

Pressing the Silence Alarm button puts the unit into Mute mode. In this mode the green Mute LED will 

illuminate and remain illuminated until Silence Alarm is pressed again. Audible Alarm indicators will be 

silenced, but all other alarm functionality remains the same, see Table 3-1.

Summary of Contents for FP1208-F-5A

Page 1: ...FlexPoint TM Series UPS Technical Manual FlexPoint 1208 F 1232 D 1250 D Series Indoor UPS Effective September 2015...

Page 2: ...ZARD WARNING provides flammability safety information to PREVENT INJURY OR DEATH to the technician or user WARNING FIRE HAZARD WARNING FIRE ELECTRICAL HAZARD ATTENTION The following sections contain i...

Page 3: ...Alpha Technologies or the nearest Alpha representative Alpha shall not be held liable for any damage or injury involving its enclosures power supplies generators batteries or other hardware if used or...

Page 4: ...ery options 8 Table 2 1 12Vdc output connector pin assignments 11 Table 3 1 Audible alarms and visual indicators 14 Table 3 2 FlexPoint battery options 14 Table of Contents FlexPoint safety and compli...

Page 5: ...signed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in...

Page 6: ...0Hz power receptacle provides primary power to the input of the unit The AC voltage is then converted to a usable 12Vdc output The power supply is to be installed within 8 2 4m of an AC receptacle Cur...

Page 7: ...either 32W or 50W respectively of 12Vdc primary and standby power for FTTx and RFoG activity The FP1208 F provides 8W of 12Vdc standby power for RFoG applications 5 1Ah 7 2Ah and 8 0Ah battery options...

Page 8: ...ceptacle Plug the line cord into the receptacle in the unit Secure line cord at one of the cable tie holes with one included cable tie Do not plug the unit into an AC receptacle until the last step of...

Page 9: ...2015 7 48 190 0 mm 3 19 81 0 mm 4 23 107 4 mm 6 57 166 9 mm 2 52 64 0 mm 2 83 71 8 mm 4 29 108 9 mm 3 23 82 0 mm Cover removed for clarity 1 0 Introduction continued 1 6 FlexPoint dimensions Fig 1 5...

Page 10: ...t the cord is easily accessible Always mount the unit in a vertical orientation with 6 15 2 cm of space above and below 2 4 5 10 cm in front and 2 5 cm of space on both sides to provide adequate therm...

Page 11: ...f the installation procedure E Connect the output cable to the 12Vdc output connection 3 and to the coaxial connector 4 Secure in cable dressing holes 5 with the included cable ties 1 2 4 3 3 4 2 Cabl...

Page 12: ...ry in place 3 Connect the battery wires to the battery terminals see Fig 2 5 To ensure correct wire connections verify the battery polarity clip is connected to the negative battery terminal 4 Install...

Page 13: ...tacle Within approximately 30 seconds the alarm should sound for 1 second it may take longer to trigger this alarm if the load is very light or not connected AC mode LED Green will display then turn o...

Page 14: ...er supply needs to be replaced REPLACE BATT LED Red steady ON 2 beeps every 15 minutes The unit automatically initiates a battery test every 180 days If the unit fails the test this alarm is triggered...

Page 15: ...e the test is postponed until those conditions are met If the AC input is lost or the unit is overloaded during the battery test it will be aborted and post poned until conditions are valid Once a bat...

Page 16: ...attery lb kg 1 2 0 54 5 1Ah Battery weight lb kg 3 9 1 8 7 2Ah Battery weight lb kg 5 7 2 6 8 0Ah Battery weight lb kg 5 73 2 76 Estimated Battery Runtimes 1 5W Load 4W Load 5 1Ah Battery Hrs 34 2 12...

Page 17: ...r 5 7 2 or 8Ah Battery L x W x D in mm 6 6 x 7 5 x 3 2 167 6 x 190 5 x 81 3 Unit Weight without Battery lb kg 1 3 0 59 5 1Ah Battery Weight lb kg 3 9 1 8 7 2Ah Battery Weight lb kg 5 7 2 6 8 0Ah Batte...

Page 18: ...7 2 or 8Ah Battery L x W x D in mm 6 6 x 7 5 x 3 2 167 6 x 190 5 x 81 3 Unit Weight without Battery lb kg 1 4 0 64 5 1Ah Battery Weight lb kg 3 9 1 8 7 2Ah Battery Weight lb kg 5 7 2 6 8 0Ah Battery...

Page 19: ......

Page 20: ...se Thorley Bishop s Stortford Hertfordshire CM22 7PA United Kingdom Tel 44 1279 501110 Fax 44 1279 659870 Alphatec Ltd 339 St Andrews St Suite 101 Andrea Chambers P O Box 56468 3307 Limassol Cyprus Te...

Reviews: