Installation and Wiring
2-1
Storage and Installation Environment
Storage Environment
Temperature -20
℃
~70
℃
Relative Humidity
≦
95%
Installation Environment
A proper installation environment not only ensures the effective operation of the
UPS but also reduces the chance of failure and extends service life. Please take the
following recommendations into account to select the most suitable environment and
reduce the likelihood of accidents.
Temperature 0
℃
~40
℃
(20
℃
~25
℃
is recommended for extend batteries life
time).
Relative Humidity
≦
95% (without condensation)
Altitude 1000m at normal power. Over 1000m above sea level, the maximum
output current must be derated by 1% every additional 100m.
This product must not be used in an environment with sparks, smoke or gas
to prevent arcing, injury and fire hazards.
Avoid using dusty materials, volatile gases, or corrosive substances with a
high salt-content in the environment where the UPS is installed.
The installation location of the UPS should be well-ventilated. During
charging, the chemical reaction of the battery generates small amounts of
gases. If there is a crack in the battery then this may pose an environmental
hazard.
Do not place in a location near a heat source as this will shorten the battery
life.
Do not place outdoors and avoid direct exposure to sunlight.
Please ensure that the environment where the UPS is placed is free from
animals that may damage the wiring, such as: rats and other small animals.
Please ensure that the floor is strong enough to hold the UPS and battery. It
must keep the equipment stable to ensure that it won't suffer damage in a fall.
We recommend placing a fire extinguisher near the UPS in case of an
emergency.