Electric Strike
AL110
PACK CONTENTS
MOUNTING STEPS OF STRIKE
INSTALL ON METAL OR ALUMINUM DOOR FRAME
DOOR LATCH POSITION
1
For aluminum or metal door frame brackets are
supplied for assembly, refer to Figure 2. For timber
door frame refer to Figure 3. mark and drill the hole
sizes as indicated on Figure 2 and Figure 3.
2
Make sure electrical connections are followed
correctly.
3
When the door is closed, ensure that there is no
pressure on the front face of strike keeper.
4
When all the above checks are completed, secure
the strike with supplied screws and recheck
operation.
As shown in Figure 1, there must be a 1mm gap between the door latch
and the front face of strike keeper to prevent the door from exerting
pressure on the keeper when door is closed.
Read all instructions before starting installation
POWER INPUT 12 VDC or 24 VDC SUPPLY:
x 4
x 2
x 2
Remove
rubber plug
prior to
assembly of
extension lips
(2 places)
Depth of lip
cutout will
vary due to
width of door
frame and
mounting
technique
25mm, 50mm,
75mm,
extension lips
are available
options
Fig.1
Fig.2
Note: There is no polarity on power input. AL110
model is not equipped with monitoring sensor.
RED
RED
YELLOW BLUE
BLUE YELLOW
BLACK
BLACK
DSS (Door Status Sensor) BLACK (COM) BLUE (NO)
ORANGE (NC)
DSS contact rating: max, current 100 mA, max.
voltage 30 vDC
1
2
3
4
12 vDC/
200 mA
24 vDC/
100 mA