• From main panel, run 6-2 with ground to outside disconnect.
• Run 6-2 with ground from outside disconnect to spa.
• ALPS SPAS recommends that a 60 AMP 220 GFCI
must be used in disconnect.
• Disconnect must be at least 6 ft. from spa!
• Any of the four panels can be drilled out and removed for
easy electrical entry.
• Wire may be drilled thru bottom of spa on wood deck or see page
12 for concrete slab location.
• All exposed wire must be INSTALLED IN CONDUIT and have
proper connectors.
• ALPS SPAS is not responsible for any mis-wiring of control panel.
• All models require a 60 AMP GFCI.
ALUMINUM WIRE WILL VOID WARRANTY!
Swim Spa electrical requirements
From main panel install a 60 AMP GFCI 220 breaker.
Run no# 6-3 with ground.
(2 hots, neutral and ground - 4 wires)
Install an outside disconnect (with 60 AMP GFCI Breaker)
No closer than 6 ft from SPA!
Hard wire from disconnect to Swim Spa control panel.