Installation
Assembly of the circuit breaker on--site
G31--201EN12
16/20
04--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Safety instructions for busbar dielectric test
(IF APPLICABLE)
REMINDER
ALSTOM Grid S.A. declines all responsibility for damages resulting
from no respect of here above recommendations
Immediate Test
Procedures
If the dielectric test is planned for this phase of installation, it is essential to
follow the instructions below.
Procedure with a CT
D
Current transformer
-- at power frequency up to 50 kV RMS, each secondary winding must be ear-
thed.
-- for a lightning impulse, it is recommended that you dismantle the CTs and
remove them from the duct.
VT Procedure
D
Potential transformer(s) with a fuse
It is imperative to :
-- remove the fuse,
-- dismantle the braid from the fuse--holder on the circuit breaker or discon-
nector connections,
It is then imperative to :
-- place each secondary winding in an earthed and short--circuit configura-
tion.
D
Potential transformer(s) without a fuse
It is imperative to :
-- dismantle the braid linking the P1/H1 (primary terminal) to the PT on the
circuit breaker or disconnector.
It is then imperative to :
-- place each secondary winding in an earthed and short--circuit configur-
ation.
Procedure with
a capacitor
D
Capacitor
It is imperative to :
-- disconnect and remove the capacitor, together with its braid, from the cir-
cuit breaker.
Procedure with a
lightning arrester
D
Lightning arrester
It is imperative to :
-- disconnect and remove the lightning arrester, together with its braid, from
the circuit breaker.
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...