Installation
Measuring main circuit resistance
G31--401EN02
5/10
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Measuring main resistance procedure of single circuit --breaker
, continued
Position of material
put in position ”LOCAL” (manual operating mechanism), the operating
mechanism,
-- circuit--breaker closed,
-- disconnector opened,
-- earthing switch(es) or starting disconnector (if applicable) opened.
Process
D
Establish a direct current at least 100 A between the input and output of
the apparatus to be tested.
D
Connect the measuring equipment on the holes allowed.
D
Measurement (
R1
) of voltage decrease between these two points gives
the resistance value at the rate of 100
m
V for 1
m
Ω
.
100 A
100 A
R1
Hole
Ø 4
R1
Hole
Ø 4
Reminder
The resistance on each apparatus must be less than the value given in
“ACCEPTANCE CRITERIA”.
Refer to the document “ACCEPTANCE CRITERIA”, see summary for refer-
ence.
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...