Installation
Connection with preparation of electrical contact surfaces
G31--501EN04
4/8
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Installing connections
Flexible connectors
The flexibleconnectors must
immediately
be attached to the connectorplate
once the contact surfaces have been prepared.
Fasten the connections between circuit--breaker and busbar using screws,
tighten to the appropriate torque.
BRAID CONNECTIONS AND
SCREWS NOT SUPPLIED BY
ALSTOM
daNm
Circuit-breaker
layout
VS...GAD01D
Important
information
With regards junctions crossed by the installation’s rated current, contact
resistance/braid must not exceed 0,5
m
Ω
..
This measure will be realized before all commissioning.