GRID
Preparing the SF
6
gas bottle
Process
The table below gives the steps of preparing the SF
6
gas bottle :
Step
Action
Diagram
1
Remove the cover (4) and plug (5)
from the SF
6
gas bottle (6).
5
4
6
SF
6
2
Fit the pressure reducer (8) on the
SF
6
gas bottle (6).
6
8
SF
6
3
Briefly open the SF
6
gas bottle tap
(7) and the cock(9) of the pressure
reducer to eliminate any air inside
the piping (approx. 20 s at low
flow--rate).
7
Open
9
Closed
SF
6
4
Close the SF
6
gas bottle tap (7)
and thecock (9)of the pressure re-
ducer.
NOTE
: Keep the end of the
tube (10) in high position to
keep the SF
6
gas which it con-
tains and to prevent damp air
from entering.
7
10
Closed
9
SF
6
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...