Commissioning
Pre--commissioning inspections
G34--001EN04
6/8
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Test operations of disconnector(s)
(if applicable)
Introduction
The measurement values demanded hereafter are to be taken during the test
and inspection programme prior to commissioning and checked with the val-
ues of the “ acceptance criteria” and checking points end of this sheet, then
entered in the pre-commissioning test report (RES..., see summary for refer-
ence) which should then be sent for approval to
ALSTOM Grid S.A. Cus-
tomer Service.
If, however, the values do not conform with those foreseen in the acceptation
criteria or general characteristics, contact
ALSTOM Grid S.A. Customer
Service.
Closing time
Measure, on each pole, the time lapse between current emission in the coil
of the closing contactor of the disconnector and the moment when
contacts touch in the pole.
Opening time
Measure, on each pole, the time lapse between current emission in the dis-
connector opening electro-magnet and the moment when contacts separate
in the pole.
Locking by means of
locks
Check that all keys required for locking are present.
Check that the locking functions of disconnector and earthing switch(es) are
operating correctly, in accordance with the interlocking diagram, at both ope-
ning and closing of apparatus.
Position signalisation
Check thatdisconnector position indicatorsareoperatingcorrectly on themi-
mic diagram.
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...