Maintenance
Maintenance plan
G51--001EN07
4/18
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Maintenance plan of earthing switch
(if applicable)
(10000 guaranteed mechanical cycles)
Maintenance
frequency
Under normal operating conditions, the maintenance plan of earthing switch
may be defined as follows :
Type of
examination
Frequency
Comment
Maintenance
visits
Once or twice a year
It is advisable to perform at
least 2 CO duty cycles per
year, when apparatus are
scarcely used, in order to
check that the earthing
switch and associated con-
trol circuits are working
properly.
Inspections
Every five years
This necessitates apparatus
shutdown.
Overhaul
Perform when one of the fol-
lowing criteria is reached :
D
operating time
≥
20 years
However, it is recommended
to proceed with inspection of
the pole or earthing switch
used the most, then to adapt
the maintenance programme
for the other apparatus
depending on the results
observed.
Intervention following
a guaranteed max-
imum short--circuit
Under the specific conditions of a guaranteed maximum short--circuit, pro-
ceed as below:
Type of
examination
Frequency
Comment
Intervention
After a guaranteed
maximum short--circuit
After
overhauling
the
earthing
switch,
it
is
recommended that you
carry out at least 2 C--O
cycles with the aim of
checking its correct func-
tioning.
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...