Maintenance
Electrical wear limits
G51--051EN03
1/2
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Electrical wear limits
Estimation
Electrical wear can be determined by means of the curve below. This curve corre-
sponds with the formula :
0<I<10 kA
Σ
I
1.2
<12000 kA
1.2
(*)
(*) Normal guarantee. In certain special operation conditions, other values may be
guaranteed.
Diagram
Electrical endurance load current
N
u
m
b
e
r
o
f
i
n
t
e
r
r
u
p
t
i
o
n
s
1
10
100
1 000
10 000
100 000
0
10
20
30
40
50
60
70
80
90
100 110
120 130 140 150 160
kA
Current tables
Admissible short circuit currents:
Current (kA)
Number of interruptions
160
2
140
2
120
3
100
4
80
6
63
10
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...