Maintenance
Replacing the electrical contact densimeter
G51--161EN02
2/4
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Removing the densimeter
Process
The table below gives the steps of removing the densimeter :
Important
information
The densimeter has been checking
and its volume is isolated from the
pole SF
6
gas volume.
(see module ...51--101)
Step
Action
Diagram
1
D
Disconnect the cable (22) of
the densimeter (2).
2
22
G
A
S
2
D
Press on the valve of the fill-
ing tool (14), venting to atmo-
spherethevolumeofthedensi-
meter.
14
3
Once venting to atmosphere is
finished :
D
Replace the valve--cap (15)
on the filling tool (14).
D
Remove the filling tool (14).
14
10
15
4
Reinstall the plug (10), apply-
ing a tightening torque of
4 daN.m,
leak tightness is
only guaranteed if this con-
dition is respected
.
5
D
Unscrew and Remove the
densimeter (1) of the SF
6
checking block (2).
D
Remove and destroy seal
(23).
1
23
2
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...