Description and operation
Pole operation of circuit--breaker
(Interrupting principle)
G13--001EN02
2/4
02--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Schematic diagram
Opening
On receiving a manual or electrical open order, the energy accumulated in the
operating mechanism’s opening spring (32) is freed.
The control lever (30), activated by the opening spring (32), transmits the
movement to the lower pole lever (34) via the rod linkage (31), in turn moving
the moving contact (11), thus separating the contacts.
Representation of
“OPEN” state
30
31
34
32
11
Closing
On receiving a manual or electrical closure order, the energy accumulated in
the operating mechanism’s closing spring (33) is freed.
This operates the moving contact (11) and closes the Interrupter Chamber.
11
Representation of
‘CLOSED’ state
33
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...