Function description
FK 3-12 spring operating mechanisms
For circuit breakers
06.04.2011
48-020-212EN02
10/15
Closing operation
70.25
70.22
70.21
70.20
79.04
71.32
70.05
70.07
70.06
70.10
70.11
70.05 Closing latch
70.21 Auxiliary switch
70.06 Closing magnet
70.22 Motor limit switch actuating cam
70.07 Manual CLOSE release
70.24 Motor limit switch
70.09 Closing shaft
70.25 Closing spring
70.10 Cam disc
70.26 Closing chain
70.11 Roller lever
70.29 Crank journal
70.12 Main shaft
70.31 Spring position indicator
70.16 Trip latch
70.52 Cicuit breaker position indicator
70.18 Operating lever
71.32 Pair of winding lever with return-stop
70.19 Trip chain
71.43 Crank lever
70.20 Trip spring
79.04 Gearing
•
Circuit breaker and operating mechanism are in operating state 2.
Operating state
2: steady
Motor
Closing
Opening
•
Closing latch 70.05 is released by the electrical command to closing
magnet 70.06 or by actuation of mechanical manual release 70.07.
•
Closing shaft 70.09 is accelerated by the effect of closing spring 70.25,
which is attached to crank lever 71.43.
70.19
70.52
70.18
70.12
70.16
70.26
70.24
70.31
70.09
71.43
70.29
B
Summary of Contents for FKG1X
Page 2: ......
Page 7: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 13: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 17: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 21: ...GRID High Voltage Switchgear This page is intentionally blank...
Page 75: ...This page is intentionally blank This page is intentionally blank...