Storage > 2 years,
continued
Closed and protected
storage area
continued
D
Check the densimeter contact threshold every five years (see ”Checking
the contact densimeter threshold”).
D
Measure the contact resistance every 5 years (see ”Main circuit resistance
measurements”).
PROTECTTHEELECTRICALCABINETAGAINSTDUST(THEELECTRI-
CAL CABINET MUST BE COVERED BUT NOT AIRTIGHT).
ANY CHANGE OF LOCATION OF THE APPARATUS (EVEN AFTER COM-
MISSIONING) SHOULD BE DONE AT A REDUCED PRESSURE OF
0.03 MPa.