GEM80
5. Operation
Issue 002 (07/05)
Fieldbus Technical Manual T2035
Page 9
Table 5-2 P-Table Example
P74
300
Pointer to P300
P300
@4801
Module #1
P301
@7910
P302
@9040
Profibus Master
P303
100
100 ms scan
P304
@0047
P305
1000
P306
100
P307
@0048
P308
2000
P309
50
P310
@0046
P311
500
P312
25
P313
0
P314
0
P315
0
G Table
G1000
Length 100 entries, 200 bytes.
H table
H2000
Length 50 entries, 100 bytes
F Table
F500
Length 25 entries, 50 bytes.
P316
@4802
Module #2
P317
@7910
P318
@9051
DeviceNet Master
P319
0
Free running
P320
@0047
P321
1100
P322
50
P323
@0048
P324
2050
P325
100
P326
@0046
P327
F525
P328
25
P329
0
P330
0
P331
0
G Table
G1100
Length 50 entries, 100 bytes.
H table
H2050
Length 100 entries, 200 bytes
F Table
F525
Length 25 entries, 50 bytes
@ Denotes a Hexadecimal Value, .i.e. all other values are decimal
5.2.1
Validity Flag (Pn and Pn+12)
The first P-table entry of each module’s configuration data contains a validity flag. Its
function is to prevent an uninitialised ‘P’-table from being used as configuration
parameters. The user must insert the hexadecimal value @4801 (module #1) or
@4802 (module #2) into the relevant table entry to signify that the module
configuration data is valid.
The insertion of any other value into the table entry renders inactive the associated
Fieldbus module.