GEM80
7. Hilscher System software (SyCon)
Issue 002 (07/05)
Fieldbus Technical Manual T2035
Page 25
7.5
Download Configuration
The download of the completed configuration file is achieved using a TCP/IP
connection over Ethernet. For this reason the GEM80-500 TCP/IP Ethernet module
must be configured and operational.
Refer to Publication T2011EN GEM80 Ethernet Modules Technical Manual for
configuration and commissioning instructions.
The Sycon configuration tool automatically connects to the well known port number
1099, the user is not required to make a port selection. A correctly configured GEM80-
500 TCP/IP Ethernet module will automatically create a port numbered 1099. It is not
necessary to supply this port value in the Ethernet module configuration.
From the configuration window select –
ONLINE
then
DOWNLOAD
Select the CIF TCP/IP Driver