27
Flowchart 4
Link terminals
22 and 27.
Inject
I
n into terminals
21 and 28
Link terminals 26 and 27.
Inject
I
n into terminals
25 and 28.
Monitor TP4 (Note 3)
Monitor R1 (Note 6)
Inject
I
n into terminals
25 and 28.
Link terminals
24 and 27.
Inject In into terminals
23 and 28
Conclusion:
Faulty pcb1
Conclusion:
Faulty pcb1, pcb2
or transformer T4
Conclusion:
Relay appears to be
functioning correctly
Conclusion:
Faulty pcb1, pcb2 or
transformer T3
NO
YES
NO
NO
NO
YES
YES
YES
TP4
voltage
correct ?
(note 3)
TP4
voltage
correct ?
(note 3)
TP4
voltage
correct
?
R1
voltage
correct
?
Monitor R1 (Note 6)
Inject In into terminals
23 and 28.
Conclusion:
Faulty pcb1
YES
R1
voltage
correct
?
Monitor R1 (Note 6)
Inject
I
n into terminals
21 and 28.
Conclusion:
Faulty pcb1
Conclusion:
Faulty pcb1, pcb2 or
transformer T5
NO
YES
R1
voltage
correct
?
Is
the relay
an MBCH
06
version
?
Follow Flowchart 5
YES
NO
NO
YES
YES
YES
YES
YES
YES