28
Flowchart 5
Link terminals
16 and 27.
Inject
I
n into
terminals 15 and 28
Link terminals
2 and 27.
Inject
I
n into terminals
19 and 28.
Monitor R1
Inject
I
n into
terminals 19 and
28
Link terminals
18 and 27.
Inject
I
n into terminals
17 and 28
Conclusion:
Faulty pcb1
Monitor R1
inject
I
n into
terminals 17
and 28
Conclusion:
Faulty pcb1
Monitor R1
inject In into
terminals 1
and 28
Conclusion:
Faulty pcb1, pcb2
or transformer T7
Conclusion:
Relay appears to
be functioning
correctly
Conclusion:
Faulty pcb1,
pcb2 or
transformer T6
NO
YES
NO
NO
NO
NO
NO
YES
YES
YES
YES
Conclusion:
Faulty pcb1
YES
Conclusion:
Faulty pcb1,
pcb2 or
transformer T8
R1
voltage
correct ?
(note 6)
TP4
voltage
correct ?
(note 3)
R1
voltage
correct ?
(note 6)
TP4
voltage
correct ?
(note 3)
TP4
voltage
correct ?
(note 3)
R1
voltage
correct ?
(note 3)
YES
YES
YES
YES
YES