29
Flowchart 6
Conclusion:
Faulty pcb1, pcb2, or
transformers T1 or T2
Relay trips when
magnetizing inrush
current flows into the
power transformer
Monitor R2 (note 4).
Inject
I
n into terminals
27 and 28
Monitor TP2 (note 7).
Inject 0.5
I
n into
terminals 27 and 28
Conclusion:
Faulty pcb1 pcb2 or
transformer T1
Conclusion:
Faulty pcb1
YES
YES
YES
YES
YES
NO
NO
TP2
Voltage
correct
?
R2
Voltage
correct
?