Altec AIR CO2-PG80 Purge Gas Generator Operations and Maintenance Manual
INLET BULKHEAD
FITTING
OUTLET
BULKHEAD
FITTING
FIG 2
SECTION 4 INSTALLATION
4.1
PARTS INCLUDED
(1) CO2-PG80 Purge Gas Generator
(1) Inlet Coalescing Filter Assy.
(1) Outlet Filter Regulator Assy.
(6) Cover Screws, 6-32 x 3/8, PH, SS
(1) Operations & Maintenance Manual
4 .2 LO C AT IO N
DO NOT INSTALL THE UNIT IN AN ENVIRONMENT OF
CORROSIVE CHEMICALS, EXPLOSIVE GASES, OR AREAS
OF HIGH OR LOW AMBIENT TEMPERATURE (ABOVE 125°F
OR BELOW 33°F).
Install the unit indoors. Unit may be wall mounted or placed on
a table top.
4.3
INSTALL FILTERS
A coalescing filter is provided to be installed on the inlet to the
adsorber/dryer to remove entrained particulates, liquid moisture
and oil which can cause damage to the desiccant beds. A
particulate afterfilter is provided to be installed on the outlet of
the adsorber/dryer to remove any adsorbent media dust that
may migrate from the desiccant beds.
Using a wrench to keep inlet bulkhead fitting from turning,
install Inlet Filter Assy to left side of unit as shown in FIG 2
above. Similarly, install Outlet Filter Regulator Assy to Right
Side of unit.
4 . 4 M O U NT I N G
1.
Table top
a.
The unit comes with rubber feet installed on bottom
of cabinet for use on table top.
2.
Wall mounting
a.
Remove (6) cover screws and remove cover. While a
helper holds the unit at the mounting location, mark
the position of the (4) mounting holes at the back of
the cabinet.
Mount the cabinet
using these
mounting holes. Be sure to use proper wall mounting
anchors if mounting in drywall.
b.
Reinstall cover.
4.5
ELECTRICAL CONNECTIONS
Before plugging in unit, check the unit nameplate for electrical
characteristics. Standard electrical characteristics are 115
volt, 1 phase, 50/60 Hz. Models operating on 230 volts are
available.
IMPORTANT!: No overload protection is provided in the
adsorber/dryer and unit should be plugged/wired into a
protected circuit.
4.6
PIPING AND CONNECTIONS
Inlet and outlet tubing should be appropriate for pressure and
temperature of operation.
See specification chart for
inlet/outlet NPT thread size. Teflon tape should be used in the
makeup of joints to ensure a good, airtight fit of piping
components. Check all connections for leakage using soap
solution prior to putting unit into service.
Page 4
P/N P013253 REV B