WIRING

 

SELV 

Secondary circuit with safety extra-low voltage 

 

A.P. 

TAMPER 

Tamper circuit for opening and removal. 
Before wiring the tamper, check if the circuit 
does not exceed 60VDC/0,1A. 

 

Ac in 

The output power failure « ERR. OUT (ACin)» 
goes from 0V to an open state during a power 
failure. 

 

ERR. OUT 

Batt 

The output low battery « ERR. OUT (Batt)» goes 
from 0V to an open state when the voltage of the 
battery exceeds the level of the low battery. 

 

0V of the power supply. If there are several 
power supplies used in the same system, it is 
imperative to connect all the 0V together.  

 

DC OUTPU

T

 

Output of the power supply. 
To facilitate the connection of several devices, 
the terminals of the DC OUTPUT are doubled. 

 

BATTE

RY 

Connector of battery output wired in factory 
Recommended batteries : 12V / 2Ah  or   12V / 
7Ah lead 
Current of the battery charge limited at 250mA. 

 

AC INPU

Transformer secondary wired in the factory. 
 
 
 

DANGEROUS VOLTAGE (230VAC – 50 Hz) 

 

To connect to the electric power 
230VAC, use a cable with 2 voltage 
connectors of 1.5 mm² 
1-

   The phase and the neutral of the 

sector are plugged directly on the 
screw terminal that is on the top of the 
transformer. 

2-

 The fuse used is timed 

          

315mAT   Dim. : 5X20 mm. 

3-

 Put the power cable as shown here  

4-

 Passage of the wires 

 