3
WIRING
SELV
Secondary circuit with safety extra-low voltage
A.P.
TAMPER
Tamper circuit for opening and removal.
Before wiring the tamper, check if the circuit
does not exceed 60VDC/0,1A.
Ac in
The output power failure « ERR. OUT (ACin)»
goes from 0V to an open state during a power
failure.
ERR. OUT
Batt
The output low battery « ERR. OUT (Batt)» goes
from 0V to an open state when the voltage of the
battery exceeds the level of the low battery.
-
0V of the power supply. If there are several
power supplies used in the same system, it is
imperative to connect all the 0V together.
DC OUTPU
T
+
Output of the power supply.
To facilitate the connection of several devices,
the terminals of the DC OUTPUT are doubled.
BATTE
RY
Connector of battery output wired in factory
Recommended batteries : 12V / 2Ah or 12V /
7Ah lead
Current of the battery charge limited at 250mA.
AC INPU
T
Transformer secondary wired in the factory.
DANGEROUS VOLTAGE (230VAC – 50 Hz)
To connect to the electric power
230VAC, use a cable with 2 voltage
connectors of 1.5 mm²
1-
The phase and the neutral of the
sector are plugged directly on the
screw terminal that is on the top of the
transformer.
2-
The fuse used is timed
315mAT Dim. : 5X20 mm.
3-
Put the power cable as shown here
4-
Passage of the wires
2
3
4
1