Configuration
GB
UnP1:
Parameters
Index
Value
Meaning
Antifreeze temperature
P024
3
4
5
...
16 (default)
...
19
20
Antifreeze protection inactive
2.0 °C
2.5 °C
...
8.0 °C
...
9.5 °C
10.0 °C
Pump control
Load equilibration:
Heating zones will be con-
trolled in a staggered way if
possible
Load collection:
Heating zones are
controlled collectively.
Actuator types:
NC - Normally Closed
NO - Normally Open
*If heating zone 1 is used as
pump control, it is necessary
to teach in a wall thermostat
to this heating zone, if an
adaptation of the pump pa-
rameters shall be performed.
P025
0
1
2
3
4 (default)
5
6
7
active, with load equilibration,
actuator type NC
active, with load equilibration
actuator type NO
active, with load collection
actuator type NC
active, with load collection
actuator type NO
inactive, with load equilibration
actuator type NC
inactive, with load equilibration
actuator type NO
inactive, with load collection
actuator type NC
inactive, with load collection
actuator type NO
Emergency operation
in heating mode
P026
0
1
...
25 (default)
...
99
100
0 %
1 %
…
25 %
…
99 %
100 %
Emergency operation
in heating mode
P032
0 (default)
1
…
99
100
0 %
1 %
…
99 %
100 %
UnP2:
Parameters
Index
Value
Meaning
Duration of valve pro-
tection function
P007
128
129
...
133 (default)
...
138
0 minutes
1 minute
...
5 minutes
...
10 minutes