background image

 

Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy

 

 

Tel. +39 0522 345518 – Fax +39 0522 345551 – mail: info@adelsystem.it 

www.adelsystem.com 

 

Instruction Manual All In One_r17.doc 

P

a

g

e

 1

 -

 C

h

a

p

te

r:

A

ll 

In

 O

n

e

U

n

in

te

rr

u

p

ti

b

le

 P

o

w

e

S

u

p

p

ly

 O

u

tp

u

V

d

c

All In One: U

ninterruptible 

P

ower 

S

upply

 Output Vdc

Thank you for having chosen one of our products for your work.  
We are certain that it will give the utmost satisfaction and be a notable help on the job. 

General Description  

Thanks  to  the  All  In  One  units  (DC-UPS),  it  will  be  possible  to  optimize 
power  management.  The  available  power  is  automatically  allocated 
between load and battery, supplying power to the load is the first priority 
of the unit thus it is not necessary to double the power, because also the 
power going to the battery will go to the load if the load so requires. The 
maximum available current on the load output is 2 times the value of the 
device  rated  current  In.  We  call  “Battery  Care”  the  concept  base  on 
algorithms  that  implement  rapid  and  automatic  charging,  battery  charge 
optimization  during  time,  flat  batteries  recovery  and  real  time  diagnostic 
during installation and operation. The Real Time Auto-diagnostic system, 
monitoring  battery  faults  such  as,  battery  Sulfated,  elements  in  short 

circuit,  accidental  reverse  polarity  connection,  disconnection  of  the  battery,  they  can  easily  be  detected  and 
removed by help of Blink Code of Diagnosis Led; during the installation and after sell. The continuous monitoring of 
battery efficiency, reduces battery damage risk and allows a safe operation in permanent connection. Each device 
is  suited  for  all  battery  types,  by  means  of  jumpers  it  is  possible  setting  predefined  curves  for  Open  Lead  Acid, 
Sealed Lead Acid, Gel, Ni-Cd, Ni-Mh(option). They are programmed for two charging levels, boost and charge, but 
they  can  be  changed  to  single  charging  level  by  the  user.  A  rugged  casing  with  bracket  for  DIN  rail  mounting 
provide IP20 protection degree. They are extremely compact and cost-effective. 

Main Characteristic 

 

Input: Single-phase  

115 – 230 Vac 

 

Output Load: power supply:  

24  Vdc;  3,  5,  10,  20  A;  12 

Vdc; 3, 6, 10, 35 A  48 Vdc; 5 – 10 A  

 

Output Battery: charging  

24  Vdc;  3  –  5  –  10  –  20  A; 

12 Vdc; 3 – 6 – 10 – 35 A; 48 Vdc; 5 – 10 A 

 

Suited  for  the  following  battery  types:  Open  Lead  Acid, 

Sealed Lead Acid, lead Gel and Ni-Cd  

 

Automatic  diagnostic  of  battery  status.  Charging  curve 

IUoUO,  constant  voltage  and  constant  current  Battery  Life 
Test function (Battery Care) 

 

Switching technology- 

 

Three charging levels: Boost, Trickle and Recovery

 

Protected  against  short  circuit,  Over  Load    and  inverted 

polarity  

 

Signal  output  (contact  free)  for  discharged  or  damaged 

battery  

 

Signal output (contact free) for mains or Back-UP 

 

Protection degree IP20 - DIN rail; Space saving 

Safety and warning notes 

WARNING 

– Explosion Hazard Do  not disconnect Equipment unless power  has been switched off or the area is 

known to be non-hazardous.  

WARNING 

– Explosion Hazard. Substitution of components may impair suitability for class I, Division 2. 

WARNING

 – Switch off the system before connecting the module. Never work on the machine when it 

is live. The device must be installed in according with UL508. The device must have a suitable isolating 
facility outside the power supply unit, via which can be switched to idle. Danger of fatal Injury! 

Connection (terminal and wiring): 

Cable Connection: 

The following cable cross-sections may be used: 

Solid 

(mm

2

Stranded 

(mm

2

AWG 

Torque (Nm) 

Stripping 

Length 

All In One  

(Size) 

1 Phase L N PE

Input AC 

1 Phase L N PE

Input AC 

0.2 – 2.5 0.2 – 2.5 

24 – 14 0.5 – 0.6 Nm 

7 mm  

Size 1 and 2

In: 

4.0 

6.0 

30 – 10 0.8 – 1.0 Nm 

7 mm 

Size 3 

0.2 – 2.5 0.2 – 2.5 

24 – 14 0.5 – 0.6 Nm 

7 mm 

Size 1 and 2

Out:

4.0 

6.0 

30 – 10 0.8 – 1.0 Nm 

7 mm 

Size 3 

Signal: 0.2 – 2.5 0.2 – 2.5 

24 – 14 0.5 – 0.6 Nm 

7 mm 

All types 

 

 

The connection is made by the screw type 2.5 mm

 or 4.0 mm

(CBI2420A – CBI1235A) terminal blocks. Use only 

copper cables that are designed for operating temperatures of > 75 °C. Wiring terminal shall be marked  to indicate 
the proper connection for the power supply. 

P

a

g

e

 3

 -

 C

h

a

p

te

r:

 

O

p

e

ra

ti

n

g

 a

n

d

 D

isp

la

E

le

m

e

n

t:

 

Output Load (Main input ON) 

The output Load in normal mode, Main Input Vac Voltage present, follow the charging battery dc output voltage. The 
minimum and maximum range stabilized are the following: 
- CBI12xx:11 – 14,4 Vdc; (Without battery connected out. Voltage fixed at 12Vdc) 
- CBI24xx:22 – 28.8 Vdc; (Without battery connected out. Voltage fixed at 24Vdc) 
- CBI48xx:44 – 57.6 Vdc; (Without battery connected out. Voltage fixed at 48Vdc) 
Thanks  to  the  All  In  One  units,  it  will  be  possible  to  manage  the  power.  The  available  power,  is  automatically 
allocated between load and battery: supplying power to the load is the first priority of the unit; thus it is not necessary 
to double the power, and also the power available for the battery will go to the load if the load requires so: 
in “Power Boost Mode” the maximum current on the load output is the 2 times the rated current 2 x In (I

load 

= I

n

+ I

batt

in continuous operation and 3 times the rated current 3 x In (I

load 

= 2I

n

+ I

batt

)  for 4 seconds; after this parameter the 

devices is electrically protected against overload and short circuit. 

- In “Power Boost Mode”, if the current of the battery generate current to the load for a time more than 4 minutes, the 

device give message (8 Blink), consequently means that the battery it is going to unloading. 

- If  the  Main  Input  Voltage  fall  below  a  Threshold  level  (50%  of  the  Typ.  Vac  input)  the  battery  it  is  immediately 

connected to the Output Load, without any interruption. 

- voltage dips: In this situation the voltage in the output load it is the same of the battery.  

To Avoid deep battery discharge, 

the battery will supply the load until battery voltage reaches 1.5 V/cell. Below 

this level the device automatically switches off to prevent Deep discharge and battery damage. 

Output Load In Buffer Mode (Main input OFF) 

Some example of buffering time depending on LOAD Output in function to the Ah of the battery. 

Buffering 
Time 

BATT1.2 Ah BATT 3 Ah 

BATT7.2 Ah 

BATT12 Ah 

BATT100 Ah 

Load 1.5 A 

20 min 

60 min 

200 min 

400 min 

Load 3 A 

8 min 

30 min 

120 min 

240 min 

Load 5 A 

3 min 

15 min 

55 min 

100 min 

Load 7.5 A 

2 min 

10 min 

30 min 

60 min 

Load 10 A 

No 

7 min 

20 min 

45 min 

20 h 

Load 12 A 

No 

3 min 

12 min 

30 min 

600 min 

Load 15 A 

No 

No 

9 min 

20 min 

400 min 

Load 20 A 

No 

No 

7 min 

13 min 

240 min 

Operating and Display Element: 

No. 10: Input AC Port pin. L – N: 

1 Phase Switching Power Supplies L, N, PE  . 
Size 2 and Size 3 BRIDGE ONLY for input 115 Vac, and connect L, N, PE  . 

No. 3: Battery Connection Port: 

Connect the battery between pin. 3 (–) and 4 (+) 
One battery (12 Vdc) for CBI12xx;  
Two battery (12 Vdc) connected in Series for CBI24xx;  
Four battery (12 Vdc) connected in Series for CBI48xx;  

No. 4: Output Load: 

Connect this Output to the load 1 (-). 2 (+). 

10

11

12

13

14

Size 1 

Size 2 

Size 3 

11

12

12

10

10

11

15

P

a

g

e

 5

 -

 C

h

a

p

te

r:

 

O

p

e

ra

ti

n

g

 a

n

d

 D

isp

la

E

le

m

e

n

t:

 

No. 12: Battery Management Configurations 

Preliminary Operations: One device for all battery types. 
Completely  automatic,  all  devices  are  suitable  to  charge  most  batteries  types  thank  to  User  Selectable  charging 
curves. They can charge open lead acid, sealed lead acid, Gel and Ni-Cd, Ni-MH batteries. It is possible to change 
or add other charging curves connecting the device to a portable PC. 
Caution:  Switch  off  the  system  before  Setting  the  jumper.  Only  jumper  in  position  5  Refresh  ON/OFF  state  whit 
Power. 

Battery Type 

Selection 

Jumper Position 

(Size 1 and Size 3) 

Jumper Position  

(Size 2) 

Trickle/Float charge 

(Volt/Cell) 

Fast/Bulk charge 

(Volt/Cell) 

Open Lead 

2.23 

2.40 

Sealed Lead Low 

2.25 

2.40 

Sealed Lead High 

2.27 

2.40 

Gel Battery 

2.30 

2.40 

Gel Battery (1)

2.30 

2.40 

NiCd – NiMh (1)

10% Imax Trimmer 

1.70–(12V);1.5–

(24V) 

Functional Setting 

Function 

Battery Life test ON 

Jumper present: 
Life test enabled. 

Fast Charge Enable 

Jumper present: 
fast charge enabled. 

“Battery Start” 

(without Input Main) 

(2) 

RTCONN  cable  for  connection  to  external 
Push bottom mounted on front Panel of the 
external system. 

Fast Recovery  

Charge (3) 

Not available 

Jumper  present:  Fast  Recovery  Charge, 
enabled  only  for  Size  3.  Possibility  to 
recharge the battery also when the voltage is 
close to Zero with the maximum power of the 
device.  To  be  careful,  the  Load  Output 
voltage follow the voltage of the battery. 

Notice:  

Be care full, in NiCd-NiMh Option, the Sealed Lead High charging curve is deleted. 
NiCd-NiMh  (Options  to  be  defined  by  Order).  End-of-charge  determined  by  negative 

V  detection  of  battery 

voltage (-5mV/cell). If no negative 

V but only a “flat” profile is detected fast charge is terminated after 10 min. 

General  end-of-charge  timeout  set  to  16  hours.  Trickle  charge  current  is  regulated  at  10%  of  max  current 
corresponding to trimmer position. In order to detect end-of-charge negative 

V, charging current must be set at 

least at 30% of nominal battery capacity (0,3 C); with lower values of charging current negative 

V detection is 

not guaranteed. 

Don’t  leave  the  juper  in  position  5;  penalty  discharge  in  Back  up  mode  completely  the  battery  close  to  Zero.  
For Size 2: must be require CBI2410A/S or CBI485A/S ( /S means  start  with battery functions, otherwise only 
start with Input Main) 

Jumper selection n.7 is available only on CBI 420W and 480W (Size 3) 

No. 5: Charging Level Current: 

It  is  possible  set  the  max  recharging  current  for  the  batteries  by  trimmer  (Charging 
Level). The current adjustment goes from 20% ÷ 100% of In. Set the maximum charging 
current between 10% and 20% of the battery capacity. 

No. 11: Auxiliary Output 

RJ 45 behind the label in SIZE 1 and SIZE 3; remove the window label to find the connector, 
For SIZE 2: CBI2410 and CBI485 require /ARJ code for RJ45 connector. 
It is possible connect: 

 

Temperature  sensor,  for  ambient  temperature  charging 
compensation.  With  this  it  is  possible  to  active  the 

specifications of the EN54-4 firing norm. 

 

Connection for external display to remote N° 3 led  of the internal 
device. 

P

a

g

e

 7

 -

 C

h

a

p

te

r:

 

P

ro

te

ct

io

n

 F

e

a

tu

re

Charging Curve 

Automatic  multi-stage  operation  and  real  time  diagnostic  allows  fast  recharge  and  recovery  of  deep  discharged 
batteries,  adding  value  and  reliability  to  the  system  hosting  the  CBI  device.  The  type  of  charging  is  Voltages 
stabilized and Current stabilized IUoUo. 
Three charging modes are identified by a flashing code on a Diagnosis LED. 
To maintain the Output Load in lower Voltage state, don’t put jumper in position 5, in this case no boost charge but 
only Float charge. 

State 

Diagnosis LED 

Battery Fault LED 

Trickle 

1 Blink/sec 

OFF 

Boost 

2 Blink/sec 

OFF 

Charging Type 

Recovery 

5 Blink/sec 

OFF 

Compensation Recharges in temperature  

(For SIZE 2: CBI2410 and CBI485 require /ARJ code) 

Connecting to RJ45 Auxiliary Output the cable RJTEMP (supplied separately), the CBI will vary the voltage of battery 
charging in depending of the temperature: 

CBI Model 

Fast Charge 

Trickle charge 

CBI12xx (12Vdc) 

-2.5mV/°C 

-1.5mV/°C 

CBI24xx (24Vdc) 

-5mV/°C 

-3mV/°C 

CBI48xx (48Vdc) 

-10mV/°C 

-6mV/°C 

The sensor place on cable RJTEMP must be applied on the battery. 
If the sensor is not connected or if the sensor is defective, the led Low Batt is on and the led Diagnosis continues to 
show the status of the battery: trickle charge, fast charge or recovery charge. 

Protection Features 

On the primary side:

 the device is equipped whit an internally fuse. If the internal fuse is activated, it is most probable 

that there is a fault in the device. If happen, the device must be checked in the factory. 

On the secondary side Battery and load:

 The device is electrically protected against short circuits and overload. 

Inversion polarity:

 the module it is automatically protected against inversion of battery polarity and connection of load 

inverted. 

Over current and output short circuit: 

 the unit limits the output current (see the technical data). 

Deep discharge : 

not possible. The unit disconnects the battery when a minimum voltage level is reached. 

P

a

g

e

 2

 -

 C

h

a

p

te

r:

 

O

u

tp

u

P

o

w

e

co

n

n

e

ct

io

n

s

Output Power connections: 

Normal connection  

Typical application for All In One device, one output for Load 
“DC Bus”, one Input/Output for connection to the battery. 
N°1 battery (12 Vdc) for CBI12xx;  
N°2 battery (12 Vdc) connected in Series for CBI24x x;  
N°4 battery (12 Vdc) connected in Series for CBI48x x;  

Parallel connection “Redundancy” 

Power  supplies  can  be  paralleled  for  1+1  redundancy  to 
obtain  a  higher  system  availability.  Redundant  systems 

require a certain amount of extra power to support the load in 
case  one  power  supply  unit  fails.  The  simplest  way  is  to  put 
two  CBI  in  parallel.  In  case  one  power  supply  unit  fails,  the 
other  one  is  automatically  able  to  support  the  load  current 
without  any interruption. This  simple  way to  build a  redundant 
system has two major disadvantages: 

The faulty power supply can not be recognized.  

- The Diagnosis LED will give the informations about the status 
of  the  Load  and  the  Battery  (see  Display  Signals  for  more 

data).It does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a 
-virtually nearly impossible - case, the defective unit becomes a load for the other power supplies and the output 
voltage  can  not  be  maintained  any  more.  This  can  only  be  avoided  by  utilizing  decoupling  diodes  which  are 
included  in  the  Redundancy  Module  MR220.  Recommendations  for  building  redundant  power  systems:  a)  Use 
separate input fuses for each CBI. b) Monitor the individual CBI units by three LED. Each unit has two relay: Mains 
or backup and Low Battery or Battery Replacement (faulty situation). This feature reports a faulty unit; see Relay 
Contact  Rating  for  any  technical  detail.  c)  When  possible,  connect  each  power  supply  to  different  phases  or 
circuits. 

Parallel connection “Double Power” 

Power supplies can be paralleled for 1+1=2 parallel to obtain a 
the  double  power  of  a  single  unit.  The  possibility  to  put  in 
parallel connection it is only in SIZE 3 devices, to be reach the 
sum of the current at the same output voltage. It is necessary 
to  use  a  standard  UTP  cable  RJ45  to  connect  Aux2  of  each 
device.  The  communication  protocol  is  based  on  CAN2.0A 
standard. In this way the system have only One output for the 
Load  and  One  output  for  the  battery.  a)  Use  separate  input 
fuses  for  each  CBI.  b)  Configure  one  unit  as  master  and  the 

other  as  slave  (see  “master/slave  network  configuration”).  User  interface  elements  (jumpers,  charging  level 
trimmer, start button, time-buffering rotary switch, thermal sensor, relays) must be used on master only, not on the 
slave. Set charging level trimmers at the same level both on master and on slave. In this configuration mode, only 
the Master device give Display status Led indications and Signal port output mains/backup and low battery. Don’t 
use Slave  device for signal  status  but only for Power unit, only the Led  Diagnosis it is  always ON  to identify the 
Slave Device. 

Master/slave network configuration 

1.  Switch  off  the  units  and  connect  RJ45  cable  in 

Aux 2 

2.  Set  rotary  switches“Time  Buffering”  in,  master:  0; 

slave: 1 

3.  Switch  on  the  units  together;  hereafter  the  rotary 

switch  on  Master  device,  is  available  for  Time 
Buffering setting. 

The  network  remains  so  configured  as  long  as  RJ45 
cable  remains  connected.  If  you  want  to  reconfigure 
the network: 

4.  Switch off the units and disconnect RJ45 cable; 
5.  Switch on the units together 
6.  Go back to point 1. 
For  Start  Battery  without  mains  voltage,  push  start 
button  only  on  Master  (the  Slave  will  powerup 
sequentially). 
In  such  double  power  connection,  all  battery  tests  are 
under master control and synchronization 

Serial connection: 

a)  It  is  possible  to  connect  as  many  units  in  series  as  needed, 
providing the sum of the output voltage does not exceed 150Vdc. 
b) Voltages with a potential above 60Vdc are not SELV any more 
and  can  be  dangerous.  Such  voltages  must  be  installed  with  a 
protection  against  touching.  c)  For  serial  operation  use  power 
supplies  of  the  same  type.  d)  Earthing  of  the  output  is  required 
when  the  sum of the output voltage is  above  60Vdc. e)  Keep  an 
installation  clearance  of  10  mm  (left/right)  between  two  power 
supplies  and  avoid  installing  the  power  supplies  on  top  of  each 
other.  Note:  Avoid  return voltage  (e.g. from  a  decelerating  motor 
or battery) which is applied to the output terminals.

P

a

g

e

 4

 -

 C

h

a

p

te

r:

 

O

p

e

ra

ti

n

g

 a

n

d

 D

isp

la

E

le

m

e

n

t:

 

No. 1, 2 Signal Ports (output Isolated): 

Connections for, 
No. 2: Main/Back Up: Input Main On/Off. Contact: 5,6,7 
No. 1: Low Battery, Fault connections systems, Battery replacement. Contact: 8,9,10 

Relay Contact Rating:  

Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A : Resistive load (EN 60947-4-1) 

Min.1mA at 5 Vdc: Min. permissive load 

Signal Output port true 
table:

Port N°2 - Led N°6 Main/Back-

Up 

Port N°1 - Led N°6 Fault 

Battery 

 

 

5-6 Closed 

5-7 Closed 

8-9 Closed 

(OK) 

8-10 Closed 

ON 

 - led off 

 

 - led off 

 

Main Input Vac 

OFF 

 

 - led On (1) 

 - led off 

 

YES 

 

 - led On 

 

 - led On 

The battery in 

BackUP it is less than 

30% cap? 

NO 

 

 - led On 

 - led off 

 

YES 

 - led off 

 

 

 - led On (2) 

Battery or system 

Fault? 

NO 

 - led off 

 

 - led off 

 

Note: 
(1) For better efficiency of the system, filter relay Main/Back up with a delay of at least 5 seconds before give alarm 
Main Lost, example: connection to PLC. 
(2) See Diagnosis Led 

No. 6, 7 and 8 Display Signals 

No.6: Led Main/Back Up: Input Main On/Off 
No.7: Led Low Battery(capacity less than 30%), Fault connections systems, Battery replacement. 
No.8: Led Battery charge mode,  
          Led Diagnosis. Diagnosis of the system through “blinking code” signal  

Monitorin

g Control 

Chart: 

State 

LED Diagnosis 
(No.8) 

LED Battery 
Fault (No.7) 

Trickle 

1 Blink/sec 

OFF 

Boost 

2 Blink/sec 

OFF 

Charging 

Type 

Recovery 

5 Blink/sec 

OFF 

Reverse polarity or high battery Voltage (over 32.5Vdc for 
CBI24xxA) 

1 Blink/pause 

 

ON 

Battery No connected 

2 Blink/pause 

 

ON 

Element in Short Circuit 

3 Blink/pause 

 

ON 

Over Load or short circuit on the load 

4 Blink/pause 

 

ON 

Bad battery; Internal impedance Bad or Bad battery wire 
connection.  

5 Blink/pause 

 

ON 

Life test not possible 

6 Blink/pause 

 

ON  

Bad thermal sensor 

7 Blink/pause 

 

ON 

Boost condition; battery discharge after 4 min. of overload. 8 Blink/pause 

 

ON 

Internal fault 

9 Blink/pause 

 

ON 

Low battery (under 18.5Vdc for CBI24xxA) Only if started 
from battery, no Main input. Form Jumper N°5 or Pus h 
Bottom 

10 Blink/pause 

ON 

CAN bus error 

11 Blink/pause 

Life test not possible; Parallel mode on Slave Device 

12 Blink/pause 

Bad battery wire connection; Parallel mode on Slave 
Device 

13 Blink/pause 

Auto 

diagnosis 

of the 

system 

Boost condition; battery discharge after 4 min. of overload; 
Parallel mode on Slave Device 

15 Blink/pause 

No. 9, 12: Start from Battery, No Main Vac 

No. 9: Push-bottom, for 3 sec., in the front panel for switch ON the system without the “Main input Vac” but 
only the battery connected. ( Not present in CBI2410XX and CBI485XX) 
No.12:  (Jumper  n.5)  It  is  also  available  the  same  function  for  remote  start  from  the  battery,  via  RTCONN 
cable connected in the Push bottom mounted on front Panel of the external system. Standard function for all 

products, Size 2 only with code CBI2410A/S and CB485A/S. 

P

a

g

e

 6

 -

 C

h

a

p

te

r:

 

B

a

tt

e

ry

 C

a

re

 

No. 13: Time Buffering Setting 

Time buffering it is enabled when the Input main is switched OFF. It is possible setting by the position of the rotate 
switch present in model SIZE 3, for the other devices, must require the time buffering fro the factory. 
The output LOAD time ON depending on position of the Switch. 
Switch positions: 

Switch position 

Time Buffering (min.) 

0.5 

10 

15 

20 

30 

45 

60 

If the switch is in 0 position the Time Buffering maintain ON state until the battery it is completed discharged. Anyway 
to prevent risk of damage, the product disconnect the batteries when a minimum voltage level is reached. 

No. 14: Auxiliary Output “Aux 2” 

Present only in CBI2420A and CBI1235A it is provided of CAN2.0A connection. 
Connection for external Intelligent display. 

No. 15: Auxiliary Output “Aux 3” 

Present only in CBI2420A and CBI1235A : Not used. 

Battery Care 

The  Battery  Care  philosophy  is  base  on  algorithms  that  implement  rapid  and  automatic  charging,  battery  charge 
optimization during time, flat batteries recovery and real time diagnostic during installation and operation. The Real 
Time Auto-diagnostic system, monitoring battery faults such as, elements in short circuit, accidental reverse polarity 
connection,  disconnection  of  the  battery,  they  can  easily  be  detected  and  removed  by  help  of  Blink  Code  of 
Diagnosis Led; during the installation and after sell. Each device is suited for all battery types, by means of jumpers it 
is  possible  setting  predefined  curves  for  Open  Lead  Acid,  Sealed  Lead  Acid,  Gel,  Ni-Cd(option).They  guarantees 
battery reliability in time by continuously testing the internal impedance status, avoids any possible risk of damages 
and grants also a permanent, reliable and safe connection of the battery to the power supply. The system, through a 
battery  stimulation  circuit  with  algorithms  of  evaluation  of  the  detected  parameter,  is  able  to  recognize  sulphated 
batteries or batteries with a short-circuited element. 
Battery Test: Automatic. Every 60 sec. check battery connection. Every 220 minute in trickle charge, make the test of 
the battery efficiency. The fault is signalized with relay commutation and diagnosis led blinking. 

Diagnostic Type Checks:  
Check for accidental disconnection of the battery cables: 

All In One detects accidental disconnection and immediately switched off the output power. 

Battery not connected: 

If the battery is not connected no output power. 

Test of quality wire connections: 

During trickle charge the quality (resistance) on the battery connection is checked every 20 sec. This to detect if the 
cable connection has been properly made. 

Battery in Open Circuit or Sulphated: 

Every 220 minute. All In One tests of internal impedance, in trickle charging mode. 

Reverse Polarity check: 

If the battery it is connected with inverted polarity, All In One is automatically protected. 

Test of battery voltage connections: 

Appropriate voltage check, to prevent connection of wrong battery types, more or less than the nominal voltage. 

End of Charge check

  

When the battery it is completely full, the device automatically switch in trickle charging mode. 

Check for Battery Cells in short circuit  

Thanks to specific algorithms of evaluation, the CBs recognize batteries with cells in internal short circuit. 
In trickle charge every 2 hours test of element in short circuit. 

Diagnosis of battery and device 

All CBI devices support the user during installation and operation. A Blink code of Diagnosis Led allows to discriminate 
among various possible faults. 
Error conditions, “LED Battery Fault” ON and “LED Diagnosis” blinking with sequence; see Display Signal section. 

P

a

g

e

 8

 -

 C

h

a

p

te

r:

 

T

h

e

rm

a

b

e

h

a

vi

o

u

Thermal behaviour 

Surrounding  air  temperature  50°C.  For  ambient  tempe rature  of  over  50°C,  the  output  current  must  be  red uced  by 
2.5%  per  °C.  Max  70°C  At  the  temperature  of  70°C  th e  output  current  will  be  50%  of  In.  The  equipment  does  not 
switch  off  in  case  of  ambient  temperature  above  70°C  or  thermal  overload.  The  devices  are  protected  for  Over 
temperature conditions “worst case”; in this situations the device Shut-down the output and automatic restart when 
temperature inside fall. 

Standards and Certification 

Electrical Safety: 

Assembling device: UL508, IEC/EN 60950 (VDE 0805) and EN 50178 (VDE 0160). 
Installation according: IEC/EN 60950. 
Input / Output separation: SELV EN 60950-1 and PELV EN 60204-1. Double or reinforced insulation. 

EMC Standards Immunity: 

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5. 

EMC Standards Emission: 

EN 61000-6-4, EN 61000-6-3, EN 61000-3-2 (see data sheet for each device) 

Standards Conformity: 

Safety of Electrical Equipment Machines: EN 60204-1. 

 The CE mark in According to EMC 2004/108/EC and Low voltage directive 2006/95/EEC 

Norms and Certifications 

In Conformity to: IEC/EN 60335-2-29 Battery chargers; EN60950 / UL1950; Electrical safety EN54-4 Fire Detection and 
fire alarm systems; 89/336/EEC EMC Directive; 2006/95/EC (Low Voltage); DIN41773 (Charging cycle); Emission: IEC 
61000-6-4; Immunity:  IEC 61000-6-2. CE. 

Rail Mounting: 

All modules must have a minimum vertical and horizontal distance of 10 cm to this power supply in order to 
guarantee  sufficient  auto  convection.  Depending  on  the  ambient  temperature  and  load  of  the  device, the 
temperature of the housing can become very high! 

Summary of Contents for CBI Series

Page 1: ...it is possible to set predefined charging curves for those battery types The available charging options are recovery boost and trickle charge All CB devices are built in a rugged metal case with a DIN...

Page 2: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 3: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 4: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 5: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 6: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 7: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 8: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 9: ...us one Input Output for connection to the battery N 1 battery 12 Vdc for CBI12xx N 2 battery 12 Vdc connected in Series for CBI24x x N 4 battery 12 Vdc connected in Series for CBI48x x Parallel connec...

Page 10: ...1min 1min 1min 1min 1min 1min 1min Trickle Float charge Typ at IN Carica di mantenimento 13 75Vdc 13 75Vdc 13 75Vdc 13 75Vdc 27 5Vdc 27 5Vdc 27 5Vdc 27 5Vdc 55Vdc 55Vdc Recovery Charge Carica di recup...

Page 11: ...1min 1min 1min 1min 1min 1min 1min Trickle Float charge Typ at IN Carica di mantenimento 13 75Vdc 13 75Vdc 13 75Vdc 13 75Vdc 27 5Vdc 27 5Vdc 27 5Vdc 27 5Vdc 55Vdc 55Vdc Recovery Charge Carica di recup...

Page 12: ...1min 1min 1min 1min 1min 1min 1min Trickle Float charge Typ at IN Carica di mantenimento 13 75Vdc 13 75Vdc 13 75Vdc 13 75Vdc 27 5Vdc 27 5Vdc 27 5Vdc 27 5Vdc 55Vdc 55Vdc Recovery Charge Carica di recup...

Reviews: