DE-3000+ IOI 8-15
All rights reserved © ALTRONIC, LLC 2015
3
2.2 The MIDAS HMI available with the DE-3000+ system uses a status strip to
display the controller status on top of all the screens. The 10 inch screen dis-
plays colored trends for analog values and temperatures, and bar graphs for all
the PIDs. In addition, log files can be stored on the SD card, if mounted on the
MIDAS HMI.
2.3 The MIDAS HMI communicates with the DE-3000+ computer module through
the Modbus TCP/IP protocol. The DE-3000+ computer module has to be cor-
rectly configured to establish communication with the MIDAS HMI.
3.0 COMPUTER MODULE (DE-3000+)
3.1 The Computer Module is designed to be rail-mounted and is the interface be-
tween the Terminal and 10" MIDAS HMI and to other systems. It typically plugs
directly into the Terminal Module using the DB-25 connectors and is held to-
gether with screws and screw locks.
3.2 The computer module must be supplied with 10-32VDC, .2A Max current.
3.2 The computer module comes with a default IP address of 10.1.100.100. In
order to configure the DE-3000+, connect it to a computer through the CAT 5e
cable and type in the default IP address on the web browser. The Home page
appears. User can navigate to the Network Settings and Port Settings by click-
ing on the menu on the left of the web page.