background image

ReServ 

 - 3 -

Installation Instructions:

This installation should be made by qualified service personnel and should conform to all local codes and in accordance 

with the National Electrical Code. Product is intended for indoor use only. This product contains no serviceable parts.

1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the

 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s

 

upper keyholes over the two upper screws, level and secure. 

 

Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. 

 

Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten 

 

all screws (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 

 

Note: This product needs to be secured to the building before operation.

2.  Connect AC power mains to the terminals marked [L & N] (Figs. 1-3, pg. 5-7).

 

Use 18 AWG or larger for all power connections (Battery, output) (Figs. 1-3, pg. 5-7).

 

Use 18 AWG to 22 AWG for power-limited circuits (AC Fail/Low Battery reporting) (Figs. 1-3, pg. 5-7).

 

Note: A readily accessible disconnect device shall be incorporated in the building installation wiring.

3.  The LEDs on the power supply board will illuminate when AC power is present.

4.  Measure output voltage before connecting cameras/devices to the outputs. This helps avoiding potential damage.

5.  ReServ3 only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the board prior

 

to connecting devices.

6.  Connecting cameras/devices:

 

ReServ1 -  Connect 12VDC cameras/devices to the terminals marked [P 1-4, N 1-4] (Fig. 1, pg. 5).

 

 

 

 

Connect 24VAC cameras/devices to the terminals marked [5-16] (Fig. 1, pg. 5).

 

ReServ2 -  Connect 24VAC cameras/devices to the terminals marked [1-16] (Fig. 2, pg. 6).

 

ReServ3 -  Connect 12VDC cameras/devices to the terminals marked [P 1-16, N 1-16] (Fig. 3, pg. 7).

7.  Connect batteries to the terminals marked [--  BAT + ] (Figs. 1-3, pg. 5-7). Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included).

 

Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH), Ultratech UT1270 (12V/7AH).

8.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Figs. 1-3, pg. 5-7)

 

supervisory relay outputs.

9.  The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present (Figs. 1-3, pg. 5-7).  

 

Note: If any of the power LEDs are not illuminated, the cause may be due to the following:

 

a.  AC mains and battery fail.

 

b.  One (1) or more power output PTCs are tripped due to a short circuit or overload condition.

 

c.  Unit damaged/defective.

 

 

To reset the PTC:

 

 

1.  Disconnect corresponding camera/device connected to terminals marked [1-16] (Figs. 1-3, pg. 5-7).

 

 

2.  Eliminate the trouble condition (short circuit or overload).

 

 

3.  Allow 1 minute for PTC to cool off (reset).

 

 

4.  Connect corresponding cameras/devices to terminals marked [1-16] (Figs. 1-3, pg. 5-7).

 

 

5.  Power LEDs will illuminate indicating power has been restored to outputs (Figs. 1-3, pg. 5-7).

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes and 
in accordance with the National Electrical Code.

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Summary of Contents for ReServ1

Page 1: ...A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2 Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3 Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs Rev 082510 More than just power ...

Page 2: ...ies 4A 100VA max load at 24VAC Two 2 12VDC 7AH 45 minutes Two 2 12VDC 12AH 90 minutes ReServ3 Stand by Batteries 8A 100VA max load at 12VDC Two 2 12VDC 7AH 45 minutes Two 2 12VDC 12AH 90 minutes When using 12AH batteries or larger a separate UL Listed battery enclosure must be installed Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Out...

Page 3: ...s devices to the terminals marked P 1 4 N 1 4 Fig 1 pg 5 Connect 24VAC cameras devices to the terminals marked 5 16 Fig 1 pg 5 ReServ2 Connect 24VAC cameras devices to the terminals marked 1 16 Fig 2 pg 6 ReServ3 Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 3 pg 7 7 Connect batteries to the terminals marked BAT Figs 1 3 pg 5 7 Use two 2 12VDC batteries connected in serie...

Page 4: ...osed NC and C are open BAT FAIL NO C NC Form C dry contacts used to signal low battery voltage or loss of battery voltage Under normal con ditions terminals marked NO and C are open NC and C are closed During a trouble condition termi nals marked NO and C are closed and NC and C are open BAT Stand by battery connections Maximum charge current 0 7A ReServ Board Terminal Legend Function Description ...

Page 5: ...arately Supervised Non power limited CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited 24VAC Power Limited Outputs 12VDC Power Limited Outputs Note Two 2 12VDC rechargeable batteries connected in series required power limited AC DC ...

Page 6: ...able Battery order separately Supervised Non power limited CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited Note Two 2 12VDC rechargeable batteries connected in series required power limited 24VAC Outputs AC DC ...

Page 7: ...rect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited Note Two 2 12VDC rechargeable batteries connected in series required 12VDC Power limited Outputs P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13 14V adjust...

Page 8: ...onix com Lifetime Warranty Made in U S A IIReServ F15P 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm Enclosure Dimensions H x W x D approximate ...

Reviews: